3-1-4 Safety Output Parameters

Parameter name
S
Safety Output
Channel Mode
S
Dual Channel Safety
Output Mode
I/O Comment
Maintenance
Counter Mode
Choice
Threshold
Maintenance
Counter

3-1-5 Operation Time Parameters

Parameter name
Equipment Name
Threshold Response
Time
Value
Not Used
Safety
Safety Pulse Test
(Can be set the
DST1-MD16SL-1
only.)
Single Channel
Dual Channel
32 characters max.
Time
Count
0 to 4,294,967,295
hours
Value
32 characters max.
0 to 65,535 ms
(in increments of 1
ms)
3-2
Description
The safety output is not used.
(External output device not connected.)
Specifies not outputting the test pulse
when the output is ON. Contact between
the output signal line and the power
supply (positive) when the output is OFF
and ground faults can be detected.
Outputs the test pulse when the output is
ON. Contact between the output signal
line and the power supply, and short
circuits with other output signal lines can
be detected.
Specifies using Single Channel Mode.
When Single Channel is set, the safety
output that would be paired for the dual
channel parameter is also set to Single
Channel Mode.
Specifies using Dual Channel Mode.
When both of the safety outputs to be
paired are normal, the outputs can be
turned ON.
Sets an I/O comment for the safety
output. The I/O comment set here is used
as the I/O tag in the Logic Editor.
Sets the operating mode for the
maintenance counter.
Sets the threshold value for the
maintenance counter.
Description
Sets a comment for the operation time to
monitor.
Sets the threshold value for the operation
time.
Remote I/O Allocations
Default
Not Used
Dual
Channel
None
Time
0
Default
None
0 ms
3-5