2-5 Node Address

2-5
Node Address
Set the node address using the two rotary switches on the front panel of the
DST1-series Safety I/O Terminals. The default setting is 63. Set the tens digit of the
node address (decimal) using the left rotary switch and set the ones digit using the right
rotary switch. A value between 00 and 63 can be set.
If a node address between 64 and 99 is set, the node address can be set from the
Network Configurator.
The node address must be set while the communications power supply is
turned OFF.
Do not change the rotary switches while the power is ON. The DST1-series
IMPORTANT
Safety I/O Terminals will detect this as a change in the configuration and
will switch to fault state.
Use a small flat-blade screwdriver to set the rotary switches, being careful
not to scratch them.
2-6

Configuration

Configure the DST1-series Safety I/O Terminals using the Network Configurator.
Refer to Section 3 Configuration for details on settings. Refer to the System
Configuration Manual (Cat.No.Z905) for Network Configurator operating procedures.
2-6
Ones digit of node address
Tens digit of node address