Omron DeviceNet DST1 Series Operation Manual page 40

Safety i/o terminals
Hide thumbs Also See for DeviceNet DST1 Series:
Table of Contents

Advertisement

Input Delays
ON Delay
An input signal is treated as being OFF during the ON delay setting time (0 to 126 ms,
in increments of 6 ms) after the input contact's rising edge. The input will turn ON only if
the input contact remains ON after the ON delay time has elapsed. This helps prevent
chattering of the input contacts.
IIN
Remote I/O data
Safety input
OFF Delay
An input signal is treated as being ON during the OFF delay setting time (0 to 126 ms,
in increments of 6 ms) after the input contact's falling edge. The input will turn OFF only
if the input contact remains OFF after the OFF delay time has elapsed. This helps
prevent chattering of the input contacts.
IN
Remote I/O data
Safety input
1-4 Description of Safety Functions
ON
OFF
ON
OFF
ON delay
ON
OFF
ON
OFF
OFF delay