3-1-2 Safety Input Parameters

Parameter name
S
Off On Delay
S
Off On Delay
S
Safety Input Channel
Mode
S
Safety Input Test
Source
S
Dual Channel Safety
Input Mode
S
Dual Channel Safety
Input Discrepancy
Time
I/O Comment
Maintenance
Counter Mode
Choice
Threshold
Maintenance
Counter
IMPORTANT When the Safety Input Channel Mode is set to Test Pulse from Test Out,
specify the test output to use for the test source and set the Test Output
Channel Mode of the test output to Pulse Test Output.
Value
0 to 126 ms
Sets the OFF/ON delay time.
(in increments of
6 ms)
0 to 126 ms
Sets the ON/OFF delay time.
(in increments of
6 ms)
Not Used
The safety input is not used.
(External input device not connected.)
Test Pulse from
Specifies connecting a device with a
Test Output
contact output in combination with a test
output. When this mode is selected, select
the test output to use for the test source
and then set the test output mode to Pulse
Test Output. When these settings are
made, contact between the input signal
line and the power supply (plus) and short
circuits with other input signal lines can be
detected.
Specifies connecting a safety device with
Used as Safety
a semiconductor output, such as a light
Input
curtain.
Specifies connecting a standard device
Used as Standard
(i.e., a non-safety device).
Input
Not used
If the channel mode of a safety input is set
to Test Pulse from Test Out, the test
Test Output 0
output is selected for use in combination
Test Output 1
with the safety input. Set the channel
Test Output 2
mode of the test output selected here to
Test Output 3
Pulse Test Output.
Single Channel
Specifies using Single Channel Mode. If
Single Channel is selected, the safety
input that would be paired for the dual
channel parameter will also be set to
Single Channel Mode.
Dual Channel
Specifies using the Dual Channel
Equivalent
Equivalent Mode with a paired safety
input.
Dual Channel
Specifies using Dual Channel
Complementary
Complementary Mode with a paired safety
input.
0 to 65,530 ms
Sets the time to monitor the logic
(in increments of
discrepancy in the dual channel input
10 ms)
logic.
32 characters
Sets an I/O comment for the safety input.
max.
The I/O comment set here is used as the
I/O tag in the Logic Editor.
Time
Sets the operating mode for the
maintenance counter.
Count
0 to
Sets the threshold value for the
4,294,967,295
maintenance counter
hours
3-2
Remote I/O Allocations
Description
Default
0 ms
0 ms
Not Used
Not Used
Dual
Channel
Equivalent
0ms
None
Time
0
3-3