Trial Operation

5.2.1 Power ON

5.2

Trial Operation Procedures

5.2.1 Power ON

5.2.2 Checking the Display Status

5.2.3 Initializing Constants

5
J
Checkpoints before Turning ON the Power Supply
Check that the power supply is of the correct voltage.
D
200 V class: 3-phase 200 to 230 VDC, 50/60 Hz
400 V class: 3-phase 380 to 460 VDC, 50/60 Hz
Make sure that the motor output terminals (U, V, W) and the motor are connected correctly.
D
Make sure that the Inverter control circuit terminal and the control device are wired correctly.
D
Set all Inverter control circuit terminals to OFF.
D
When using a PG Speed Control Card, make sure that it is wired correctly.
D
Make sure that the motor is not connected to the mechanical system (no-load status)
D
If the Digital Operator's display at the time the power is connected is normal, it will read as follows:
Normal
When an fault has occurred, the details of the fault will be displayed instead of the above display. In that
case, refer to Section NO TAG Maintenance Operations. The following display is an example of a fault
display.
Fault
When replacing the controller PCB, check the Inverter capacity (kVA) in o2-04 first and then initialize
D
constants to the factory settings. There is no need to initialize constants the first time trial operation
is performed after purchasing the Inverter.
To initialize the constants, set "2220" in A1-03 (Initialize).
D
After initialization, the access level is set to Quick-start (A1-01). The following table shows the setting
D
method for Quick-start.
Use the following procedure to initialize constants.
Step
Key Sequence
1
MENU
2
3
DATA
ENTER
4
Press 3 times.
5
DATA
ENTER
6
7
DATA
ENTER
8
ESC
Frequency Ref
The frequency reference monitor is
displayed in the data display section.
U1--01 = 0.00 HZ
UV
The display will differ depending
on the type of fault.
Under Voltage
Digital Operator Display
Frequency Ref
U1--01 = 0.00 HZ
MC5
Main Menu
Operation
MC5
Main Menu
Initialize
Select Language
English
Initialize
Select
A1-03 = 0
Select
A1-03 = 2220
2--wire Initial
Entry Accepted
Initialize
Select
MC5
Main Menu
Initialize
- 4
Remarks
Displays operation mode.
Displays initialize mode.
Puts the Inverter in initialize mode.
Displays the Initialize display.
Displays the constant setting for
A1-03.
Initializes for a 2-wire sequence.
Writes the set values. "Entry Accept-
ed" is displayed for approximately
0.5 seconds.
Returns to the Initialize display.
Returns to the initialize mode display.