User Constants
8.2.6 Terminal Constants: H
Constant
Constant
Number
Number
Multi-function input 4
H1-04
(terminal 6)
Multi-function input 5
H1-05
(terminal 7)
Multi-function input 6
H1-06
(terminal 8)
*
The values in parentheses indicate initial values when initialized in 3-wire sequence.
Setting
Setting
value
0
3-wire sequence (Forward/Reverse run command)
1
Local/Remote selection (ON: Operator, OFF: Constant setting)
2
Option/Inverter selection (ON: Option card)
Multi-step speed reference 1
3
When H3-05 is set to "0," this function is combined with "Master/auxiliary speed switch."
4
Multi-step speed reference 2
5
Multi-step speed reference 3
6
Jog frequency reference (higher priority than multi-step speed reference)
7
Accel/Decel time 1
8
External baseblock NO (NO contact: Baseblock at ON)
9
External baseblock NC (NC contact: Baseblock at OFF)
A
Accel/Decel ramp hold (ON: Accel/decel stopped, frequency on hold)
B
OH2 alarm signal input (ON: OH2 will be displayed)
C
Multi-function analog input selection (ON: Enable)
E
Speed control integral reset (ON: Integral control disabled)
F
Not used. (Do not input this setting.)
10
Up command (Always set with the down command)
11
Down command (Always set with the up command)
12
FJOG command (ON: Forward run at jog frequency d1-09)
13
RJOG command (ON: Reverse run at jog frequency d1-09)
14
Fault reset (Reset when turned ON)
8
15
Emergency stop (ON: Deceleration to stop in emergency stop time C1-09)
16
Motor switch command (Motor 2 selection)
1A
Accel/Decel time 2
Constants write enable (ON: All constants can be written-in. OFF: All constants other than
1B
frequency monitor are write protected.)
1C
Trim control increase (ON: d4-02 frequencies are added to analog frequency references.)
Trim control decrease (ON: d4-02 frequencies are subtracted from analog frequency refer-
1D
ences.)
1E
Analog frequency reference sample/hold
1F
Frequency reference terminal 13/14 selection (ON: selects terminal 14)
External fault (Desired settings possible)
20 to 2F
Input mode: NO contact/NC contact, Detection mode: Normal/during operation
Stopping method: Deceleration to stop, coast to stop, emergency stop or continue operation.
60
DC injection braking command (ON: Performs DC injection braking)
61
External speed search command 1: Maximum output frequency (ON: speed search)
62
External speed search command 2: Set frequency (ON: speed search)
64
External speed search command 3
65
KEB (deceleration at momentary power loss) command (NO contact)
66
KEB (deceleration at momentary power loss) command (NO contact)
77
Speed control (ASR) proportional gain switch (ON: C5-03)
80
Winding change
Name
Name
Display
Display
Terminal 6 Sel
Terminal 7 Sel
Terminal 8 Sel
Multi-function Input Functions
Setting
Setting
Factory
Factory
Range
Range
Setting
Setting
0 to 77
4 (3) *
0 to 77
6 (4) *
0 to 77
8 (6) *
Function
- 20
Change
Change
Control Methods
during
during
Open Loop
Opera-
Opera-
Flux Vector
Vector
tion
tion
B
B
B
B
B
B
Control Methods
Open loop
Flux vector
Vector
Page
Page
- 32
- 32
- 32
Page
- 13
- 32
- 32
- 13
- 13
- 13
- 13
- 16
- 32
- 32
- 33
- 33
- 33
- 33
- 34
- 34
- 16
- 16
- 35
- 16
- 35
- 16
- 36
- 36
- 36
- 37
- 16
- 37
- 40
- 40
- 40
- 41
- 67