Settings
D
Setting
0
0 to 10 VDC input [10- -bit input]
- -10 to 10 VDC input
1
(A negative voltage is a reference for reverse rotation.)
2
4 to 20 mA input
When the terminal is being used as a voltage input terminal (setting 0 or 1), jumper J1 must be discon-
D
nected on the control board. (See Figure 6.1.) The terminal's input resistor will be destroyed if the ter-
minal is used for a voltage input with jumper J1 connected.
When frequency references are being input simultaneously from both the voltage terminal 13 and the
D
current terminal 14, the final reference value will be the sum of the two references that are input.
To switch the frequency reference input between the voltage terminal 13 and the current terminal 14,
D
set a value of 1F in any one of the multi-function inputs (H1-01 through H1-06).
The voltage terminal 13 will be used when this multi-function input is OFF and the current terminal
14 will be used when this multi-function input is ON.
If a 0 to 10 VDC input is set, H3-01 must also be set to a 0 to 10 VDC input.
D
Jumper wire
J1
11 12(G)
13
14
15
1
2
3
4
5
R
T
S
©
L3
L1
L2
Power input
Fig
6.1 Terminal Arrangement of a 200 V Class Inverter of 0.4 kW
Function and Signal Level for Multi-function Analog Input (Terminal 16):
J
H3-04, H3-05
This function is useful when switching between two analog inputs. The input is from terminal 16.
D
When using the multi-function input (terminal 16) as the frequency reference terminal, first set the
D
multi-function analog input function to "Auxiliary Reference" by setting constant H3-05 to 0.
Function for Multi-function Analog Input, Terminal 16: H3-05
User
User
Constant
Number
Multi-function analog
H3-05
input (terminal 16)
The auxiliary reference is factory-preset to 0.
D
After setting H3-05 to 0, set any one of the multi-function inputs (H1-01 through H1-06) to a value
D
of 3 (multi-step speed reference 1).
When a multi-function analog input has been set to "Auxiliary Reference," it is treated as frequency
D
reference 2 during multi-step speed operation, so it can't be used unless the multi-step speed reference
1 has been set.
16
17
25
26
27
6
7
8
21
¨2
B1
B2
¨1
Braking Resistor
Change
during
during
Name
Opera-
tion
- 5
Function
33
18 19
20
22
23
9
10
V
W/T3
U
T2
T1
Motor output
CHARGE
Valid Access Levels
Setting
Setting
Factory
Factory
Unit
Open Loop
Range
Setting
Vector
0 to 1F
- -
0
6.1 C ommon Settings
Control circuit