Sensor Transmission Time And Temperature Variables; Operating Mode (Model Wds) - Trane WTS Installation, Operation And Maintenance Manual

Wireless zone sensors
Table of Contents

Advertisement

Sensor Transmission Time and Temperature Variables

Sensor transition time variables are as follows:
Note: If a sensor transmits a message to the receiver and the receiver does not reply, the sensor
Sensor temperature time variables are as follows:

Operating Mode (Model WDS)

This section describes the Trane model WDS wireless sensor operation.
example of a model WDS that has been configured and is in operating mode.
Figure 9.
Wireless sensor (model WDS) in operating mode
Test symbols (appear only when Test button is pushed
BAS-SVX04G-EN
The maximum time between sensor temperature transmissions is 15 minutes.
The minimum time between sensor temperature transmissions is 30 seconds.
The minimum time for transmitting temperature setpoint changes is 10 seconds.
will retransmit the message to the receiver every 30 seconds until communication to the
receiver is re-established.
The minimum change in zone temperature required to force a sensor transmission is:
– 0.2°F (0.11°C) when the temperature range is between 60°F (15.6°C) and 80°F
(26.7°C)
– 0.5°F (0.28°C) when the temperature range is between 32°F (0°C) and 60°F (15.6°C)
or between 80°F (26.7°C) and 122°F (50°C))
The minimum change in temperature setpoint required to force a sensor transmission is:
– 1°F (0.56°C) for a model WZS sensor
– 0.1°F for model WZS sensor
– 0.1°C for a model WDS sensor
Temperature
System settings
Occupancy indicator/Error code
Fan settings
Keypad
Test button
Operation
Figure 9
shows an
.
31