1. Observe the polarity indicators that are molded into the cover.
2. Install two batteries (of the type specified in
The sensor has been designed to prevent damage if the batteries are installed backwards, to reduce
the potential for injury.

Manual Association

At any time, the manual association method can be used to associate the receiver with the sensor.
If an association was previously established between a receiver and a sensor and needs to be re-
established, the manual association process may be used. If an association has not yet been
established, the automatic association process is recommended (see
the Receiver," p.
1. Using a small screwdriver, set the three rotary address switches
2. Set the three rotary address switches
3. Record the address and location of the receiver and sensor pair.
Note: A receiver will retain its address information through a power loss. Address information is

Disassociation

The receiver disassociates from the sensor (by removing all stored association information),
conducts a channel scan, and restarts itself, if any of the following are true:
Note: A disassociated sensor will transit an association request every 10 minutes.
BAS-SVX04G-EN
is molded into the sensor cover.
18).
S2, S3) on the receiver to an address between 001 and 999.
Notes:
• An address can be changed without powering down the receiver or sensor.
• An address can be changed at any time after initial association has been established.
same address as the receiver.
lost only if the receiver is manually disassociated or if its rotary switch setting is changed
after it has been associated.
The receiver address is changed from its current setting (001–999).
The receiver receives a disassociation notification from its associated sensor.
The receiver does not receive a communication from its associated sensor within 50 minutes.
The sensor and receiver are associated and communicating at the time the sensor is set to 000
and the Test button is pressed.
Maintenance and Troubleshooting
"Battery Type," p.
38) in the battery-holding slot that
(Figure 1, p.
11, locations S1, S2, S3) on the sensor to the
"Associating the Sensor to
(Figure 1, p.
11, locations S1,
39