Diagnostics; Testing Signal Strength - Trane WTS Installation, Operation And Maintenance Manual

Wireless zone sensors
Table of Contents

Advertisement

Diagnostics

LED1, LED2, and LED3, located on the sensor of models WTS and WZS, respond to diagnostics by
exhibiting specific blinking patterns. View their response by pressing the Test button. (See
Error codes appear on the display of the model WDS sensor when diagnostics occur. (See
Table 3.
Diagnostics on the sensor
LED state when Test button is pressed (WTS,
WZS sensors)
N/A
LED1: Off
LED2: Off
(a)
LED3
: 1-blink pattern repeated 3 times
LED1: Off
LED2: Off
(a)
LED3
: 2-blink pattern repeated 3 times
LED1: Off
LED2: Off
(a)
LED3
: 3-blink pattern repeated 3 times
LED1: Off
LED2: Off
(a)
LED3
: 4-blink pattern repeated 3 times
(a) Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repetitions.
LED1, LED2, and LED3, located on the receiver of all models, respond to diagnostics by exhibiting
specific blinking patterns. They respond independently of any user action. (See
Table 4.
Diagnostics on the receiver
LED state
LED1: Off
LED2: Off
LED3: 1-blink pattern repeated continuously
LED1: Off
LED2: Off
LED3: 2-blink pattern repeated continuously
LED1: Off
LED2: Off
LED3: 3-blink pattern repeated continuously
(a) Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repetitions.

Testing Signal Strength

To initiate a signal strength test, push the Test button on the sensor (see location of Test button in
Figure 11, p.
BAS-SVX04G-EN
Error code (WDS
sensor display)
E0, E5, E7
E1
E2
E3
E4
Indicates...
Disassociated
• Receiver is not associated, waiting for a sensor.
• Receiver lost communication with sensor.
• Receiver has no devices on its wireless personal area network.
(a)
• Association with a device has been manually removed.
Address set to 000
• Address not set to between 001–999.
(a)
Not configured
• Receiver configuration properties not properly set (defective receiver).
(a)
34).
Models WTS, WZS: LED1, LED2, and LED3 respond by indicating signal strength. You can view
them on the sensor
(Table
Model WDS: Test symbols on the sensor display indicate signal strength
and LED3, on the receiver, respond by indicating signal strength
Maintenance and Troubleshooting
Indicates...
Sensor failure
• Replace sensor
Disassociated
• Sensor is not associated with a receiver.
Address set to 000
• Address not set to between 001–999.
Software error
• Replace sensor
Input voltage too high
• No RF transmission is permitted with an input battery voltage
greater than 3.9 V.
5) and the receiver
(Table 6, p.
Table
36).
(Table
5). LED1, LED2,
(Table 6, p.
36).
Table