Mains Power Connections; Relay Output Board Connections - ABB SM3000 User Manual

Multipoint videographic recorder
Hide thumbs Also See for SM3000:
Table of Contents

Advertisement

SM3000
Multipoint Videographic Recorder

7.6 Mains Power Connections

Fuse,
400mA, Type T
Line
Neutral
Terminal Block J
Fig. 7.10 AC Power Supply
Warning. Use fuse rating – 400 mA (max.) type T.
Fuse,
3A, Type T
24V DC
Fig. 7.11 DC Power Supply
Warning. Use fuse rating – 3 A (max.) type T.
118
1
L
100 to 240 V AC ±10 %
2
N
(90 min. to 264 V max.)
3
50/60 Hz
4
5
6
7
8
1
2
3
+
4
-
5
6
7
8
Terminal Block J

7.7 Relay Output Board Connections

Note.
The maximum total combined current flowing through
the relays is 36 A. The maximum individual relay
current is 5 A.
The
polarity
is
selected
configuration – see Section 6.7.2, page 102.
17
14
11
18
15
12
19
16
13
Terminal Block E, F, G or H
Fig. 7.12 Relay Connections
Note. Relay contacts are fitted with arc suppression
components as standard.
7 Installation
during
I/O
module
7
4
1
8
5
2
9
6
3
IM/SM3000–EN Rev. L