I/O Module Configuration; Analog Inputs - ABB SM3000 User Manual

Multipoint videographic recorder
Hide thumbs Also See for SM3000:
Table of Contents

Advertisement

SM3000
Multipoint Videographic Recorder

6.7 I/O Module Configuration

Fig. 6.19 I/O Module Configuration
Note. The instrument detects the type of module fitted in each position automatically.

6.7.1 Analog Inputs

IM/SM3000–EN Rev. L
Set the mains rejection frequency used to electrical noise
induced on the signal lines by power supply cables.
Input Adjustment
Manually fine-tune inputs to remove process offset errors or
system scale errors.
Note.
Input adjustment frames appear only if recording is
enabled during configuration, i.e. the 'Disable recording in
configuration' check box is not ticked on entry to the
Configuration level – see Fig. 6.1, page 52.
Changes to the Analog Input Type (see Section 6.6.2,
page 89) must be saved to the current configuration
before commencing input adjustment.
Actual value / Desired value
1. Adjust the process or simulated input signal to a known
value below 50 % of the engineering range.
2. If 'Actual value' (in engineering units) is different from
expected, set 'Desired value' to the correct value ('Offset
adjust'
and
'Span
automatically).
3. Repeat steps 1 and 2 for a value above 50 % of the
engineering range.
4. Repeat steps 1 to 3 for each input.
Reset adjustment
Select to reset 'Offset adjust' and 'Span adjust' (see next page)
to zero and to 1 respectively.
6 Configuration
adjust'
values
are
calculated
101

Advertisement

Table of Contents
loading

Table of Contents