Annex A (configuration guide)
17.2 Configuration list
Î The functions and parameters are described in detail in the Configuration Manual u KH 6493.
...
...............
Menu Function -CO-
Control parameters
PAR
Input
IN
IN1
Input signal IN1
IN2
Input signal IN2
MEAS
Signal monitoring
17-2
or
..........................................
Setting
options
Description of functions
1)
0–20 mA
0 to 20 mA
4–20 mA
4 to 20 mA
0–10 V
0 to 10 V
2–10 V
2 to 10 V
100 PT
Pt 100 (–100 ... +500 °C)
1000 PT
Pt 1000 (–100 ... +500 °C)
100 NI
Ni 100 (–60 ... +250 °C)
1000 NI
Ni 1000 (–60 ... +250 °C)
0–1 KOHM
0 to 1000 Ω
0–20 mA
0 to 20 mA
4–20 mA
4 to 20 mA
0–10 V
0 to 10 V
2–10 V
2 to 10 V
100 PT
Pt 100 (–100 ... +500 °C)
1000 PT
Pt 1000 (–100 ... +500 °C)
100 NI
Ni 100 (–60 ... +250 °C)
1000 NI
Ni 1000 (–60 ... +250 °C)
0–1 KOHM
0 to 1000 Ω
oFF ME.MO
OFF
IN1 ME.MO
Analog input IN1
IN2 ME.MO
Analog input IN2
ALL ME.MO
Analog inputs IN1 and IN2
..................... ..................
Parameter level -PA-
IN1/mA
IN1/mA
IN1/V
IN1/V
IN1/PT
IN1/PT
IN1/NI
IN1/PT
IN1/KOHM
IN2/mA
IN2/mA
IN2/V
IN2/V
IN2/PT
IN2/PT
IN2/NI
IN2/PT
IN2/KOHM
noPA MEAS/ME.MO
Default setting is in bold print.
1)
EB 6493 EN