Î Open parameter level.
Reading: code of the first parameter
If you want to configure a different parameter:
Î Select parameter.
Î Activate editing mode for the parameter.
The code of the function parameter blinks.
Î Set the parameter.
Î Confirm setting.
After setting all parameters:
Î Press until the controller is back in the operating level.
Note
The controller automatically returns to the operating level five minutes after the last key has
been pressed.
Configuration and parameterization example
The compact controller is to configured to be a PID controller. The associated proportion-
al-action coefficient (KP) is to be set to 1.5. Refer to the overview in Annex A. This overview
shows that time behavior is defined by the C.PID function in the CNTR menu.
....
Menu
Function -CO-
Control structure and functions
CNTR
C.PID
Control algorithm
The proportional-action coefficient is set with the KP parameter.
EB 6493 EN
..............
Setting options
P CP.YP
PI CP.YP
Pd CP.YP
PId CP.YP
PPI CP.YP
Start-up and configuration at the device
................................
or
Description of functions
 1)
P behavior
PI behavior
PD behavior
PID behavior
P²I behavior
..............
Parameters -PA-
C.PID/CP.YP
C.PID/CP.YP
C.PID/CP.YP
C.PID/CP.YP
C.PID/CP.YP
7-9