Configuration list and customer settings

5 Configuration list and customer settings
Function block list
The function blocks have the following listed functions.
F = Function block
F
Function
01 DHW tapping recognition
02 Flow rate sensor
03 Adaptation
04 Direction of action
05 Current input
06 Function of current input
07 Measuring range of cur-
rent input
08 Function of binary input
09 Maintain heat exchanger
at constant temperature
10 Upper limit (GWH)
11 Lower limit (GWL)
18
WE = Default setting
WE
Meaning
1
0: Continuous control
1: Flow rate sensor active
1
0: Flow switch
1: Water flow sensor
1
0: Not active
1: Active (with water flow sensor)
0
0: >> (increasing/increasing)
1: <> (increasing/decreasing)
0
0: Not active (binary input)
1: Active
0
0: Actual value
1: Set point
0
0: 0 to 20 mA
1: 4 to 20 mA
0
0: Termination of maintaining heat exchanger at constant
temperature
1: Switchover between internal set points
0
0: Time adjustable
1: Continuous
0
0: No limitation
1: Exceeding GWH causes switch-off
0
0: No frost protection
1: Violation of GWL causes frost protection to start
KH 5757 EN