Samson TROVIS 5724-8 Mounting And Operating Instructions

Electric actuators with process controller for heating and cooling applications

Advertisement

Quick Links

EB 5724-8 EN
Translation of original instructions
Electric Actuators with Process Controller
TROVIS 5724-8 (without fail-safe action)
TROVIS 5725-8 (with fail-safe action)
For heating and cooling applications
Firmware version 1.1x/2.1x
Edition August 2019

Advertisement

Table of Contents
loading

Summary of Contents for Samson TROVIS 5724-8

  • Page 1 EB 5724-8 EN Translation of original instructions Electric Actuators with Process Controller TROVIS 5724-8 (without fail-safe action) TROVIS 5725-8 (with fail-safe action) For heating and cooling applications Firmware version 1.1x/2.1x Edition August 2019...
  • Page 2 Î For the safe and proper use of these instructions, read them carefully and keep them for later reference. Î If you have any questions about these instructions, contact SAMSON‘s After-sales Service Department (aftersalesservice@samson.de). The mounting and operating instructions for the devices are included in the scope of delivery.
  • Page 3: Table Of Contents

    Contents Safety instructions and measures ..............5 Notes on possible severe personal injury ............8 Notes on possible personal injury ..............9 Notes on possible property damage ..............10 Markings on the device ................11 Actuator nameplate ..................11 Valve nameplate ..................11 Design and principle of operation ..............12 Fail-safe positions ..................12 Operating controls ..................13 Readings and their meaning .................13...
  • Page 4 Contents 5.6.1 Protocol .......................26 5.6.2 Connection with control station ..............28 5.6.3 Configuration of the electric actuator .............29 Quick check ....................29 Operation ....................30 Adjusting the set point ..................30 Starting/end closed-loop operation ...............30 Increasing/decreasing set point ..............31 Selecting the external/internal set point ............32 Start and stop program controller ..............32 Manually changing the stem position .............33 Maintenance ....................33 Preparation for return shipment ..............33...
  • Page 5: Safety Instructions And Measures

    Therefore, operators must ensure that the actuator is only used in applications that meet the specifications used for sizing the actuator at the ordering stage. In case operators intend to use the actuator in other applications or conditions than specified, SAMSON must be con- tacted. SAMSON does not assume any liability for damage resulting from the failure to use the de- vice for its intended purpose or for damage caused by external forces or any other external factors. Î Refer to the technical data for limits and fields of application as well as possible uses. See section 3.6.
  • Page 6 − An active blocking protection (A8.3 configuration item = 1, see section 10.2) in the elec- tric actuator with process controller prevents the valve from seizing up. − Upon supply voltage failure, the TROVIS 5725-8 Electric Actuator causes the valve to move to a certain fail-safe position. The fail-safe action of SAMSON actuators is speci- fied on the actuator nameplate. Warning against residual hazards To avoid personal injury or property damage, plant operators and operating personnel must prevent hazards that could be caused in the control valve by the process medium, the operat- ing pressure, the signal pressure or by moving parts by taking appropriate precautions.
  • Page 7 The following documents apply in addition to these mounting and operating instructions: − Configuration Manual for TROVIS 5724-8 and TROVIS 5725-8 Electric Actuators with Process Controllers u KH 5724-8 − Mounting and operating instructions of the valve on which the electric actuator is mounted, e.g. for SAMSON valves: u EB 5861 for Type 3260 Three-way Valve u EB 5863 for Type 3226 Three-way Valve u EB 5866 for Type 3222 Globe Valve u EB 5868 for Type 3213 and Type 3214 Globe Valves u EB 8111 for Type 3321 Globe Valve...
  • Page 8: Notes On Possible Severe Personal Injury

    Safety instructions and measures 1.1 Notes on possible severe personal injury DANGER Risk of electric shock. Î Before connecting wiring, performing any work on the device or opening the de- vice, disconnect the supply voltage and protect it against unintentional reconnec- tion. Î Only use power interruption devices that are protected against unintentional recon- nection of the supply voltage.
  • Page 9: Notes On Possible Personal Injury

    Safety instructions and measures 1.2 Notes on possible personal injury WARNING Crush hazard arising from moving parts. The form-fit version of the electric actuator with process controller contains moving parts (actuator and plug stems), which can injure hands or fingers if inserted into the actuator. Î Do not insert hands or finger into the yoke while the valve is in operation. Î Disconnect the supply voltage before performing any work on the control valve. Î Do not impede the movement of the actuator or plug stem by inserting objects into their path.
  • Page 10: Notes On Possible Property Damage

    Safety instructions and measures 1.3 Notes on possible property damage NOTICE Risk of actuator damage due to the supply voltage exceeding the permissible toler- ances. The electric actuators are designed for use according to regulations for low-voltage in- stallations. Î Observe the permissible tolerances of the supply voltage. Risk of actuator damage due to excessively high tightening torques.
  • Page 11: Markings On The Device

    Markings on the device 2 Markings on the device 2.2 Valve nameplate 2.1 Actuator nameplate See associated valve documentation. TROVIS 5724-820 Electric Actuator with Process Controller Var.-ID 4150511.04 Serial no. 1085 *000000* F: 500 N s: 12 mm v: 0.18 mm/s U: 230 V f: 50 Hz P: 5 VA...
  • Page 12: Design And Principle Of Operation

    TROVIS 5724-8 The electric actuators with process controllers The TROVIS 5724-8 Electric Actuator with are mounted onto SAMSON Types 3222, Process Controller does not have fail-safe ac- 3213, 3214, 2488, 42-36 E, 3226 and tion. When a valve is mounted on this actua- 3260 Valves as well as Series V2001 Valves tor, the valve remains in the last position af- up to nominal size DN 50.
  • Page 13: Operating Controls

    Design and principle of operation 3.2 Operating controls Display The actual value (process variable) before the comparator for controller [1] or [2] is TROVIS 5724-8: Travel indicator handwheel shown on the display during closed-loop op- eration. The setting is performed in the A3.1 configuration item in TROVIS-VIEW. See sec- tion 10.2. 3.3 Readings and their meaning Non-blinking readings on the display Displayed value (see A.2.2) lower than...
  • Page 14: Versions

    Design and principle of operation − Programmed function of [O] key activat- No initialization (7) ed by on-site operation. No calibration (8) Stem extension/retraction canceled (9) Manual level active Time Initialization in progress − Program (program controller) active. Update in progress Note Time The number in brackets indicates the priority of the E0 to E9 errors (highest priority = 1).
  • Page 15: Accessories

    The TROVIS-VIEW software can be ing output) and two Pt 1000 sensors downloaded free of charge from our − Device version [C] with two-wire con- website (u www.samson.de at Services necting cable (supply voltage), two > Software > TROVIS-VIEW). The soft- Pt 1000 sensors and a four-wire control ware can also be supplied on a CD- line for two further inputs ROM.
  • Page 16: Technical Data

    Design and principle of operation Accessories for sensors − CrNiMo steel thermowell, G ½, 250 mm immersion length, PN 40, order no. − Mounting kit for a Pt 1000 cable sensor 1099-0806 (contact sensor), order no. 8524-0020 − Brass thermowell, G ½, 160 mm immer- − Brass thermowell, G ½, 80 mm immer- sion length, PN 16, order no. 8525- sion length, PN 16, order no. 1099- 5005 0807 − CrNiMo steel thermowell, G ½, 160 mm − CrNiMo steel thermowell, G ½, 80 mm immersion length, PN 40, order no. immersion length, PN 40, order no. 8525-5011 1099-0805 3.6 Technical data Electric actuator with process 5724- 5725- 5724-...
  • Page 17 Design and principle of operation Device • Two-wire connecting cable with open end for connection to supply voltage (5 m) version [A] • Two Pt 1000 sensors (2 m blue and 3 m red) Device • Three-wire connecting cable with open end for connection to supply voltage and version [B] switching output (2.5 m) • Two Pt 1000 sensors (2 m blue and 3 m red) Device • Two-wire connecting cable with open end for connection to supply voltage (5 m) version [C] • Two Pt 1000 sensors (2 m blue and 3 m red) • Four-wire control line for two additional inputs (3 m) Device • Three-wire connecting cable with open end for connection to supply voltage and version [D] switching output (2.5 m) •...
  • Page 18 Design and principle of operation Table 2: Function of the operating keys Function Briefly pressing the key Depending on how A2.1 configuration item is set, a set point, which can be adjust- ed, is displayed (see section 10.2). Briefly pressing the key Depending on how A2.2 configuration item is set, a different value is displayed (see section 10.2). Briefly pressing the key The function depends on how A1.1 configuration item is set (see section 10.2). Key held pressed for three seconds Reading H A Open manual level. Key held pressed for six seconds Reading I n Start initialization (see section 5.4).
  • Page 19: Dimensions In Mm

    Design and principle of operation 3.7 Dimensions in mm TROVIS 5724-810/-820 and TROVIS 5725-810/-820 TROVIS 5724-830 and TROVIS 5725-830 Ø15.8 46.5 Ø10 EB 5724-8 EN...
  • Page 20: Preparation

    − Observe storage instructions. 4.1 Unpacking − Avoid long storage times. − Contact SAMSON in case of different stor- age conditions or longer storage times. Note Do not remove the packaging until immedi- ately before mounting and start-up.
  • Page 21: Aligning The Travel Indication Scale

    Preparation 4.4 Aligning the travel Holes for driving pin with three- indication scale way mixing valve The travel indication scale has two opposed scales. Which scale is to be used depends on the valve version (Fig. 2). In the delivered state, the scale alignment applies to globe valves and three-way diverting valves.
  • Page 22: Mounting And Start-Up

    Mounting and start-up 5 Mounting and start-up 3. Pull plug stem until it reaches the actuator stem or extend actuator stem using the handwheel (2). NOTICE 4. Position the clamps of the stem connector Risk of malfunction due to incorrectly per- (16) included in the accessories on the formed start-up.
  • Page 23 Mounting and start-up Force-locking attachment with coupling nut, e.g. Form-fit attachment with stem connector, e.g. with to Type 3222 Valve rod-type yoke on Series V2001 Valve Handwheel (TROVIS 5724-8 only) Actuator stem Coupling nut Yoke Stem connector Fig. 4: Attaching actuator and valve Fig. 5: Mounting position EB 5724-8 EN...
  • Page 24 Mounting and start-up − Connect the actuator to the electrical net- Î Switch on supply voltage. work only after the supply voltage is first On starting up the actuator for the first switched off. Make sure the power cannot time, the error reading E7 (no initializa- be switched on unintentionally.
  • Page 25: Starting Initialization

    Mounting and start-up 5.4 Starting initialization Pt 1000, The actuator needs to be initialized on start- red marking – ing up the actuator for the first time. Mount Pt 1000, the electric actuator with process controller – blue marking onto the valve before initialization to ensure that the initialization values match the on-site –...
  • Page 26: Configuring The Electric Actuator

    Modbus and can be configured using from the SAMSON website (www. samson. TROVIS-VIEW. Various communications de) and is available in the [?] menu in the protocol (SSP or Modbus-RTU slave) and a TROVIS-VIEW software.
  • Page 27 Mounting and start-up Table 4: Communication parameters C P menu Designation Setting Communication unit Bluetooth module not active Bluetooth module active RS-485 module active Communication protocol Modbus-RTU slave The following values are automatically set with the 'A P' setting: b d = 96, S t = I n Automatic protocol detection Modbus address 01 to .99 01 to 99 (station address) 00.
  • Page 28: Connection With Control Station

    Mounting and start-up − Setting -2: automatic operation is reestablished. The time for the The SSP and Modbus protocols are au- bus failure monitoring is adjustable. Set the tomatically detected: the interface pa- value to 0 to deactivate bus failure monitor- ing.
  • Page 29: Configuration Of The Electric Actuator

    Mounting and start-up 5.6.3 Configuration of the electric actuator Î Connect the USB-RS485 adapter R3 to the electric actuator and computer. Î Perform configuration as required in TROVIS-VIEW. 5.7 Quick check To test the electric actuator's ability to func- tion, the following quick checks can be per- formed: Î Apply the maximum and minimum con- trol signals (e.g.
  • Page 30: Operation

    Operation 6 Operation 6.1 Adjusting the set point Immediately after completing mounting and Necessary configuration (see section 10.2) start-up, the valve with electric actuator is − A2.1 = 1 to change the set point at con- ready for use. troller [1] C1.SP − A2.1 = 2 to change the set point at con- WARNING troller [2] C2.SP Form-fit version: crush hazard arising from Adjusting the set point moving parts (actuator and plug stem).
  • Page 31: Increasing/Decreasing Set Point

    Operation 6.3 Increasing/decreasing set Start closed-loop operation point Start closed-loop operation. Readings: Necessary configuration (see section 10.2) 'on' during start-up time. Afterwards, the value resulting from the A3.1 con- − A1.1 = 2 and A1.5 = 0 or figuration item. − A1.1 = 2 and A1.5 = 1 or − A1.1 = 2 and A1.5 = 2 or − A1.1 = 2 and A1.5 = 3 or Note − A1.1 = 2 and A1.5 = 4 The duration of start-up time is set in the A1.T.ON parameter in TROVIS-VIEW.
  • Page 32: Selecting The External/Internal Set Point

    Operation 6.4 Selecting the external/in- 6.5 Start and stop program ternal set point controller The program controller allows you to define Necessary configuration (see section 10.2) the set point over time (max. 1 week = − A1.1 = 3 and A1.5 = 0 or 10080 min). Additionally, it is possible to − A1.1 = 3 and A1.5 = 1 or define the behavior after the program has − A1.1 = 3 and A1.5 = 2 or run (see A0.1 configuration item). See sec- − A1.1 = 3 and A1.5 = 3 or tion 10.2. − A1.1 = 3 and A1.5 = 4 Necessary configuration (see section 10.2) Note − A1.1 = 4 and A1.5 = 0 or The setting A1.5 = 1, 2, 3 or 4 allows the −...
  • Page 33: Manually Changing The Stem Position

    TROVIS 5724-8 only The electric actuator with process controller A manual adjustment of the stem position was checked by SAMSON before it left the only makes sense when the supply voltage is factory. switched off as the stem position is deter- −...
  • Page 34: Malfunctions

    Î Troubleshooting (see Table 5). Note Emergency action in the event of valve fail- Contact SAMSON's After-sales Service de- ure is described in the associated valve doc- partment for malfunctions not listed in the ta- umentation.
  • Page 35: Decommissioning And Disassembly

    Decommissioning and disassembly 9 Decommissioning and disas- 2. Completely drain the pipelines and valve. sembly 3. Disconnect and lock the supply voltage. 4. If necessary, allow the pipeline and valve DANGER DANGER components to cool down. Risk of electric shock. 5.
  • Page 36: Disposal

    Addresses of SAMSON AG and its subsid- iaries The addresses of SAMSON AG, its subsid- iaries, representatives, and service facilities worldwide can be found on the SAMSON website, in all SAMSON product catalogs or on the back of these Mounting and Operat- ing Instructions. Required specifications Please submit the following details: −...
  • Page 37: Configuration And Parameter List

    Appendix 10.2 Configuration and parameter list Note The default setting depends on the selected system code number. A list of all default settings is available on page 52. CO/PA Function/ Setting/ designation adjustment range I … Inputs and outputs Universal input I1/Universal input I2/Universal input I3 I1/I2/I3 Function 0: None...
  • Page 38 Appendix CO/PA Function/ Setting/ designation adjustment range AI4.I1 Input signal, point 1 0.0 to 99.9 % AI4.COR* Offset AI4 –9.9 to 9.9 % AI4.O1 Output signal, point 1 –50 to 150 °C AI4.I2 Input signal, point 2 0.1 to 100.0 % AI4.O2 Output signal, point 2 –50 to 150 °C Switching output Function None...
  • Page 39 Appendix CO/PA Function/ Setting/ designation adjustment range System code number 35: Heating · Follow-up control · Outdoor temperature controlled, return flow temperature limitation · External set point decrease with DI4 50: Heating · Override control with minimum selection · Return flow temperature limitation · Internal set point decrease 55: Heating · Override control with minimum selection · Outdoor temperature controlled, return flow tempera- ture limitation · External set point decrease with DI4 60: Cooling · Override control with minimum selection · Differential temperature with two sensors, return flow temperature limitation · Start/stop control sequence 65: Cooling · Override control with minimum selection · Differential temperature with two sensors, return flow temperature limitation · Start/stop control sequence 66: Cooling · Override control for district cooling · Maximum selection of the set point control ·...
  • Page 40 Appendix CO/PA Function/ Setting/ designation adjustment range Controller [1] active when DI3 = off / Controller Control mode [2] active when DI3 = on Controller [1] active when DI4 = off / Controller [2] active when DI4 = on Cascade Direction of action >> (increasing/increasing) <> (increasing/decreasing) Internal limit LIM1/Internal limit LIM2 LIM1.S/ Source Measured value AI1 LIM2.S Measured value AI1 after function generation Measured value AI2 Measured value AI2 after function generation Measured value AI3 Measured value AI3 after function generation...
  • Page 41 Appendix CO/PA Function/ Setting/ designation adjustment range Program controller A0.1 Behavior when program 1: Control active, last set point is retained has elapsed 2: Control active, program is repeated cyclically 3: Control inactive, actuator positioning value is 0 % 4: Control inactive, actuator positioning value is 100 % C1 .../C2 ... Controller [1]/controller [2] Actual value (process variable) (C1.a * AI1 + C1.b * AI2 + C1.c * AI3 + C1.d * AI4) C1.1/C2.1 Source...
  • Page 42 Appendix CO/PA Function/ Setting/ designation adjustment range 7: Set point = Output of controller [2] C1.2/C2.2 Source 8: Set point = Program controller 9: Set point = Program controller + C1.SP + C1.e * AI1 + C1.f * AI2 + C1.g * AI3 + C1.h * AI4 C1.SP/C2.2 Set point –50.0 to +150.0 °C C1.SP.DIF/ Set point offset –50.0 to +150.0 °C C2.SP.DIF C1.SP.MIN/...
  • Page 43 Appendix CO/PA Function/ Setting/ designation adjustment range Manipulated variable C1.4/C2.4 Function Controller positioning value Fixed actuator positioning value with DI1 Fixed actuator positioning value with DI2 Fixed actuator positioning value with DI3 Fixed actuator positioning value with DI4 Fixed actuator positioning value with LIM1 Fixed actuator positioning value with LIM2 C1.YP/C2.
  • Page 44 Appendix CO/PA Function/ Setting/ designation adjustment range Characteristic 0: Linear Characteristic type 1: Equal percentage 2: Reverse equal percentage 3: User-defined 0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0 0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0 A ...
  • Page 45 Appendix CO/PA Function/ Setting/ designation adjustment range [Up]/[Down] settings A2.1 [Up] key function Display and adjust set point C1.SP Display and adjust set point C2.SP Display set point C1.SP Display set point C2.SP Display set point before comparator of controller [1] Display set point before comparator of controller [2] A2.2 [Down] key function Display measured value AI1 Display measured value AI1 after function generation Display measured value AI2 Display measured value AI2 after function generation Display measured value AI3...
  • Page 46: Excerpt From Modbus List

    Appendix 10.3 Excerpt from Modbus list The firmware version 2.1x of TROVIS 5724-8 and TROVIS 5725-8 Electric Actuators with Process Controllers have an integrated RS-485 interface to use the Modbus-RTU protocol, which is a master/slave protocol (in which the control station acts as the master and the elec- tric actuator as the slave). The following Modbus functions are supported: Code Modbus function...
  • Page 47 Appendix Transmission range Indicating range Designation Access Start Start Device ID data Device type 5724 5725 5724 5725 Version Revision (e.g. rev. 2.00) 9999 1.00 99.99 Serial number, part 1 (four high-order digits) 9999 9999 Serial number, part 2 (four low-order digits) 9999 9999 Firmware version...
  • Page 48 Appendix Transmission range Indicating range Designation Access Start Start Manual level Manual positioning value (external) 1000 100.0 Set point deviation of the external manual 1000 100.0 level Operating values (operating function) Operating function state Operating function cause Program controller set point –500 1500 –50.0...
  • Page 49 Appendix Transmission range Indicating range Designation Access Start Start Operating values and settings of controller [2] Actual value before comparator of controller –500 1500 –50.0 150.0 [2] (PV[2]) Set point before comparator of controller [2] –500 1500 –50.0 150.0 (SP[2]) Set point deviation of controller [2] (SP[2] – –9999 9999 –999.9 999.9 PV[2]) Positioning value of controller [2] before 1000 100.0 characteristic Y[2]...
  • Page 50 Appendix Class Designation COILS (1-bit) Access Status 0 Status 1 Limits State of internal limit 1 State of internal limit 2 Limit switches State of limit switch "stem retracted" State of limit switch "stem extended" Switching output Logical state of switching output Switching contact of switching output Enable manual level for switching output Logical state (manual level for switching out-...
  • Page 51 Appendix Class Designation COILS (1-bit) Access Status 0 Status 1 EE-Error serial number cause EE-Error manufacturing parameters state EE-Error manufacturing parameters cause EE-Error manufacturing parameters state EE-Error manufacturing parameters cause EE-Error status messages state EE-Error status messages cause EE-Error statistics state EE-Error statistics cause Actions Zero calibration active...
  • Page 52: Default Settings

    Appendix 10.4 Default settings If a system code number ≠0 is switched to system code number 0, the data of previously se- lected system code number are adopted. Any parameters not used in this configured system are written with the default setting. The electric actuator with process controller is delivered with the system code number 10 (fixed set point control, heating with mean value calculation of two sensors and set point de- crease) set by default. System code number AI1.I1 °C –50 –50 –50 –50 –50 –50 –50...
  • Page 53 Appendix System code number – M4.T – – LIM1.S – – – – – – LIM1.F – – – – – – LIM1.P °C – – – – – – LIM1.H °C – – – – – – LIM2.S – –...
  • Page 54 Appendix System code number C1.f – – – – – C1.g – – – – – C1.h – – – – – C1.3 C1.KP 40.0 10.0 C1.TN s 120 C1.TV C1.Y0 C1.4 C1.YP – – – – – – – C2.1 –...
  • Page 55 Appendix System code number C2.3 – – – – – – C2.KP – – – – – – C2.TN s 120 – – – – – – C2.TV – – – – – – C2.Y0 – – – – – –...
  • Page 56: Customer Setting

    Appendix 10.5 Customer setting System code number AI1.I1 °C –50 –50 –50 –50 –50 AI1.O1 °C –50 –50 –50 –50 –50 AI1.I2 °C AI1.O2 °C AI2.I1 °C –50 –50 –50 –50 –50 –50 AI2.O2 °C –50 –50 –50 –50 –50 –50 AI2.I2 °C...
  • Page 57 Appendix System code number LIM1.S – – – LIM1.F – – – LIM1.P °C – – – LIM1.H °C – – – LIM2.S – – – LIM2.F – – – LIM2.P °C – – – LIM2.H °C – – – 10.0 C1.1 –...
  • Page 58 Appendix System code number C1.3 C1.KP 40.0 40.0 10.0 10.0 C1.TN C1.TV C1.Y0 C1.4 C1.YP – – – – – – C2.1 C2.a – – – – – – C2.b – – – – – – C2.c – – – –...
  • Page 59 Appendix System code number C2.TV C2.Y0 C2.4 C2.YP – – – – – – MY.EA MY.EE 99.0 99.0 99.0 99.0 99.0 99.0 MY.TE MY.TZ A7.1 A7.YP.ERR 100.0 100.0 100.0 100.0 A8.1 A8.2 A8.3 A1.1 A1.5 – – A1.T.ON – – A1.YP.ON 100.0 100.0 100.0 –...
  • Page 60: Electrical Connection

    Appendix 10.6 Electrical connection UI1 + UI1 – UI2 + UI2 – UI3 + UI3 – UI4 + UI4 – NOTICE The display does not work due to an interrupted cable connection. Supply − Only open the front housing cover to voltage perform actions described in these instructions.
  • Page 61: Declaration Of Conformity

    EN 61000-6-2:2005, EN 61000-6-3:2010, EMC 2014/30/EU (ab/from 2016-04-20) EN 61326:2013 LVD 2006/95/EC (bis/to 2016-04-19) EN 60730-1:2011, EN 61010-1:2010 LVD 2014/35/EU (ab/from 2016-04-20) Hersteller / Manufacturer: SAMSON AKTIENGESELLSCHAFT Weismüllerstraße 3 D-60314 Frankfurt am Main Deutschland/Germany Frankfurt, 2016-04-06 Gert Nahler ppa. Günther Scherer Zentralabteilungsleiter/Head of Department Qualitätssicherung/Quality Managment...
  • Page 62 EB 5724-8 EN...
  • Page 63 EB 5724-8 EN...
  • Page 64 EB 5724-8 EN SAMSON AKTIENGESELLSCHAFT Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 samson@samson.de · www.samson.de...

This manual is also suitable for:

Trovis 5725-8

Table of Contents