Start-Up Adaptation [Tune] - Samson TROVIS 6493 Mounting And Operating Instructions

Compact controller
Hide thumbs Also See for TROVIS 6493:
Table of Contents

Advertisement

Start-up and configuration with TROVIS-VIEW
The 'Reset to default settings' function in the AUX folder causes all parameters, functions and
calibration data to be reset to their default settings.
The System data (1) and (2) saved in the controller are not cleared.
8.2.3.8

Start-up adaptation [TUNE]

The Start-up adaptation [TUNE] folder corresponds to the TUNE main group of the controller.
It is possible to preset a start-up adaptation to automatically tune the control parameters KP,
TN and TV in this folder. In addition, the start-up adaptation can be started or canceled.
Note
The conditions for performing an adaptation are listed in the 'Start-up and configuration at
the device' section.
Starting the adaptation
1. Open the 'Operation' folder.
2. Set manual mode:
Î Set 'Manual/automatic switch' to 'Manual' and transfer the new setting to the controller.
3. Determine the set point and transfer it to the controller.
4. In manual mode, set the controlled variable to match the set point.
5. Open the 'Start-up adaptation [TUNE]' folder.
6. Enter the step response in 'Step-change value of manipulated variable [Y.JMP]' field and
transfer it to the controller.
7. Set 'Start-up adaptation' to 'Start'.
8. Right-click 'Start-up adaptation' and select 'Execute' from the context-sensitive menu.
Adaptation is started.
Exiting or canceling the adaptation
1. Open the 'Start-up adaptation [TUNE]' folder.
2. Set 'Start-up adaptation' to 'Off'.
3. Right-click 'Start-up adaptation' and select 'Execute' from the context-sensitive menu. Ad-
aptation is ended.
Note
In online mode, the adaptation progress is displayed in 'Adaptation status'.