Functions
8.5 Function Group Device Outputs
When "Split value active" is selected, the output is active when the current level of the flow value
is within the lower sub-domain 0 to "Split value". In this case the output current is scaled to the
0 to "Split value" range. If the flow value exceeds this sub-domain, the output current is scaled
to the 0 to URV range.
Note
The relay contact is open in the "no function" setting.
• Signal type, menu item 4.3.2
You can set the function of the relay as follows in this menu item:
1. When the relay need to be closed in the event of an alarm:
Flow in forward direction
Limit value message
2. When the relay need to be open in the event of an alarm:
Flow in forward direction
Limit value message
Table 8-3
Setting
1. Contact closes
2. Contact opens
①
②
Figure 8-8
NOTICE
At high inductive loads, the digital output must be protected against transient overvoltage with
a suitable external recovery diode.
The electronic fuse is tripped in the event of overloading. The recovery time of the fuse is a few
minutes. The relay contact is open in the no-load state.
70
Relay status
9
Electronic fuse
External supply
Digital output 2
No alarm
Reverse flow
No limit signalling
Operating Instructions, 03/2021, A5E00102775-AC
Alarm message
Forward flow
Limit signalling
TRANSMAG 2 with MAG 911/E