Siemens SITRANS F TRANSMAG 2 Operating Instructions Manual page 55

Electromagnetic flometers
Table of Contents

Advertisement

function for the digital outputs or 'Failure signal' for the analog output) (see menu items 4.1.2,
4.2.1 and 4.3.1).
• A flashing "F" process related error at the top right of the display indicates a process error.
• A flashing "D" at the top right of the display indicates a device error.
Should errors in groups 'F' and 'D' occur at the same time, only 'D' will flash.
In communication via PROFIBUS, the diagnostic message displayed here is also reported under
the extended diagnosis with the diagnostic bit "EXTENSION_AVAILABLE".
Table 8-1
Error messages
Error message
Measurement module failure
Calibration failure measurement module F
Simulation is running
Flow measurement unreliable
Calibration is running
Tube empty
Measuring range overflow > 110 %
COM Module failure
Memory failure
Software failure
Sensor failure
Flow measurement disturbed
For texts with more than 16 characters, the marks
device display respectively indicate that there are other characters to the left and/or right of the
displayed text. You can display these by actuating the
Electrode check (Menu item 2.2)
The electrode DC voltage is scanned cyclically when this menu item has been selected. This
detects e.g. deposits on the electrodes. If there is a fault or an error, the alarm signal 'Flow
measurement unreliable' is triggered.
Note
This function requires a sensor with SmartPLUG.
Empty Pipe Det. (menu item 2.3)
The function checks whether the electrodes of the sensor are wetted by the medium. To do this,
you have to determine the monitoring interval.
TRANSMAG 2 with MAG 911/E
Operating Instructions, 03/2021, A5E00102775-AC
Flashing indica‐
Error is Signaled
tion in display
at the analog out‐
menu
put
F
-
-
F
-
F
-
F
x
F
x
F
x
D
-
D
x
D
x
D
x
D
x
8.3 Function Group Diagnostics
Error is signaled
at digital output 1
and 2
-
-
-
-
x
x
x
-
x
x
x
x
and
in the first and last segment of the
and
operating elements.
Functions
PROFIBUS
x
x
x
x
x
x
x
-
x
x
x
x
55