Using a Programming Console
Startup Operating Mode

6-1-3 Connecting the Programming Console

Attached
cable (2 m)
CQM1-PRO01-E
C200H-CN222 (2 m) or
C200H-CN422 (4 m)
Connecting Cable
CS1W-CN224 (2 m) or
CS1W-CN624 (4 m)
Connecting Cable
C200H-PRO27-E
The operating mode of the CPM2B when the power is turned ON depends upon
the PC Setup setting in DM 6600 and the Programming Console's mode switch
setting if the Programming Console is connected.
PC Setup setting
(DM 6600)
00xx
01xx
0200
0201
0202
Note The default setting is 00xx. With this default setting, the PC will automatically
enter RUN mode if a Programming Console is not connected and SW201 is ON.
Be sure that it is safe for the PC to operate before turning it ON under these
conditions.
Connect the Programming Console's connecting cable to the CPM2B's periph-
eral port, as shown below.
CS1W-CN114
Connecting Cable
(0.05 m)
Peripheral port
connector
CPM2C-CN111
Connecting Cable
(0.1 m) (See note 2.)
Note
1. Always turn OFF SW 201 before connecting the Programming Console.
2. Only the peripheral port connector can be used when a CPM2C-CN111
Connecting Cable is connected.
Programming
Console connected
The startup mode
RUN mode if no Programming Device
determined by the
is connected. PROGRAM mode if
mode switch setting.
another Programming Device is
connected.
The startup mode is the same as the operating mode before
power was interrupted.
PROGRAM mode
MONITOR mode
RUN mode
SW201
(See note 1.)
Peripheral port
Section
Programming Console not
connected
CPM2B CPU Board
6-1
81