Specifications
Interrupt Inputs
Expansion I/O Board Input Specifications
Item
Input voltage
Input impedance
Input current
ON voltage
OFF voltage
ON delay
OFF delay
Circuit configuration
CPU Board and Expansion I/O Board Output Specifications
Relay Outputs
Item
Max. switching capacity
Min. switching capacity
Service life of relay
(See note.)
ON delay
OFF delay
Circuit configuration
Inputs IN00003 through IN00006 can be used as interrupt inputs (interrupt input
mode or counter mode) and quick-response inputs. The minimum pulse width
for these inputs is 50 µs.
+10%
24 V DC
/
–15%
4.7 kΩ
5 mA typical
14.4 V DC min.
5.0 V DC max.
1 to 80 ms max. Default: 10 ms (See note.)
1 to 80 ms max. Default: 10 ms (See note.)
IN
COM
Note The input time constant can be set to 1, 2, 3, 5, 10, 20, 40, or 80 ms in the PC
Setup. See page 66.
2 A, 250 V AC (cosφ = 1)
2 A, 24 V DC
(4 A/common)
10 mA, 5 V DC
Electrical:
150,000 operations (24-V DC resistive load)
100,000 operations (240-V AC inductive load, cosφ = 0.4)
Mechanical:
20,000,000 operations
15 ms max.
15 ms max.
Specification
4.7 kΩ
750 Ω
Input LED
Specification
Output LED
Section
2-1
OUT
COM
27