Selecting an Installation Site
!
Caution

3-2-1 Installation Site Conditions

3-2-2 Panel/Cabinet Installation

Overheating
Electrical Noise
Be sure to install the CPM2B correctly, as outlined in this manual. Failure to do so
may result in Board malfunction.
Note Do not install the CPM2B under any of the following conditions.
• Locations subject to direct sunlight.
• Locations subject to an ambient temperature below 0°C or over 55°C.
• Locations subject to an ambient humidity below 10% or over 90%.
• Locations subject to condensation as the result of severe changes in tempera-
ture.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to shock or vibration.
• Locations subject to exposure to water, oil, or chemicals.
Be sure that the conditions at the installation site conform to the CPM2B's gen-
eral specifications. Refer to 2-1-1 General Specifications for details.
Note Provide proper shielding when installing in the following locations:
• Locations subject to static electricity or other sources of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radiation.
• Locations near to power supply lines.
Consider PC operation, maintenance, and surrounding conditions when instal-
ling the CPM2B in a panel or cabinet.
The ambient operating temperature range for the CPM2B is 0_C to 55_C. Be
sure that there is adequate ventilation for cooling.
• Allow enough space for air circulation.
• Do not install the CPM2B above equipment that generates a large amount of
heat, such as heaters, transformers, or large resistors.
• Install a cooling fan or system when the ambient temperature exceeds 55_C.
Power lines and high-voltage equipment can cause electrical noise in the PC.
• Do not install the CPM2B in a panel or cabinet with high-voltage equipment.
• Allow at least 200 mm between the CPM2B and nearby power lines.
Control panel
Fan
CPM2B
Air vent
200 mm min.
CPM2B
200 mm min.
Section
3-2
37