Omron SYSMAC CPM2B Operation Manual page 18

Programmable controller
Hide thumbs Also See for SYSMAC CPM2B:
Table of Contents

Advertisement

CPM2B Features and Functions
High-speed 1:1 NT Link
Communications
One-to-one PC Link
1-1-2 Overview of CPM2B Functions
Main function
Interrupts
from a bar code reader or transmitted to a serial printer. The serial devices can
be connected to the RS-232C port or Peripheral port.
Inputting data from a bar code reader
Bar code
reader
Outputting data to a serial printer
Serial
printer
In a 1:1 NT Link, an OMRON Programmable Terminal (PT) can be connected
directly to the CPM2B. The PT must be connected to the RS-232C port; it cannot
be connected to the Peripheral port.
OMRON PT
A CPM2B can be linked directly to another CPM2B, CQM1, CPM1, CPM1A,
CPM2A, CPM2C, SRM1(-V2), C200HS or C200HX/HG/HE PC. The 1:1 PC Link
allows automatic data link connections. The PCs must be connected through the
RS-232C ports; they cannot be connected through the Peripheral ports.
CPM2B
Interrupt inputs
4 inputs, see note 1.
Response time: 50 µs
Interval timer interrupts
1 input
Set value: 0.5 to 319,968 ms
Precision: 0.1 ms
CPM2B
Variations/Details
Scheduled interrupts
One-shot interrupt
Section
1-1
CPM2B
CPM2B
CPM2B
5

Advertisement