12.4 Parameter

The motorized linear actuator eSyStep supports parameter data in the ISDU (Index Service Data Unit). Parameters can be
transmitted non-cyclically with ISDU. Block parametrization and data storage are also supported.
12.4.1 System Command
The commands required for block parametrization and data storage are transmitted with the System Command parameter.
Index
Sub-
Off-
Index
set
0x02
0
Description of parameter values
Parameter
System Command
12.4.2 Data Storage Index
Changes to the parameters are stored in the IO-Link master with the Data Storage Index parameter and restored with a IO-Link
device identical in construction when replaced. To do so, the Data Storage parameter must be enabled in the Device Access
Locks (see "Device Access Locks", page 28) parameter. The parameters are automatically replaced via the IO-Link master.
Index
Sub-
Off-
Index
set
0x03
1
2
3
4
5
www.gemu-group.com
Access
Length
Rights
W
1 byte
System Command
Values
0x01 to 0x06
Access to IO-Link
0x82
Reset product to default settings
Access
Length
Rights
R/W
1 byte
RO
1 byte
RO
4 bytes
RO
4 bytes
Parameter Checksum
RO
41 bytes
Parameter
Type
UIntegerT
Description
Parameter
Type
Data Storage
UIntegerT8
Cmd
State Property
UIntegerT8
Data Storage
UIntegerT32
Size
UIntegerT32
Index List
OctetStringT
27 / 52
12 Specific data IO-Link (pin 6)
Values
0x01 to 0x06
0x82
Values
GEMÜ 533
Positioner (Code S0)