GEM 533 eSyStep Operating Instructions Manual page 26

Motorized globe valve
Table of Contents

Advertisement

12 Specific data IO-Link (pin 6)
Index
Sub-
Access
Index
rights
0x62
1
RO
2
RO
0x90
2
R/W
3
R/W
0xB0
1
R/W
2
R/W
3
R/W
4
R/W
0xB2
1
R/W
2
R/W
0xB4
1
R/W
2
R/W
0xB6
1
R/W
2
R/W
0xB8
1
R/W
2
R/W
3
R/W
4
R/W
5
R/W
0xBA
1
R/W
2
R/W
3
R/W
4
R/W
0xBC
0
R/W
GEMÜ 533
Positioner (Code S0)
Parameter
Operating Time Open
Current operating time
Operating Time Close
Current operating time
Force
Force of average tra-
Init Force
Force of initialization
Reinforcement P kp
P component – posi-
Reinforcement D kD
D component – posi-
Derivative action time
Dead zone
Open Tight
Sealing function valve
Close Tight
Sealing function valve
Split Start
Split End
Max Pos
Min Pos
Set Value Direction
Set value direction set
Set Value Type
Determine signal input
I Min W
Determine minimum
I Max W
Determine maximum
U Max W
Determine maximum
Analog Output Dir
Set value direction set
Analog Output Type
Determine signal out-
Analog Out Min
Determine minimum
Analog Out Max
Determine maximum
Init Time
Set debounce time for
26 / 52
Function
OPEN
CLOSE
versing range and
sealing
tioner
tioner
Delay constant
Hysteresis
position OPEN
position CLOSED
Set set value start
Set set value end
Stroke limiter valve
position OPEN
Stroke limiter valve
position CLOSED
value input
current input
current input
current input
value output
put
signal output
signal output
initialization start
Factory
Setting options
settings
0
0 to 255
(0 to 25.5s)
0
0 to 255
(0 to 25.5s)
6
1 to 6
3
1 to 6
200
1 to 200
(0.1 to 20.0)
10
1 to 200
(0.1 to 20.0)
0
0 to 100
(0 to 100 s)
10
1 to 250
(0.1 to 25.0%)
995
800 to 1000
(80.0 to 100.0%)
5
0 to 200
(0 to 20.0%)
0
0 to Split End – 100
(0.0 to Split End –
10.0%)
1000
Split Start + 100 to
1000
(Split Start + 10.0% to
100.0%)
1000
Min Pos to 1000
(Min Pos to 100.0%)
0
0 to Max Pos
(0.0% to Max Pos)
0
0 → Rise (rising)
1 → Fall (falling)
1
0 → 0 to 20 mA
1 → 4 to 20 mA
2 → 0 to 10 V
35
0 to 40
(0 to 4.0 mA)
205
200 to 220
(20.0 to 22.0 mA)
103
100 to 110
(10.0 to 11.0 V)
0
0 → Rise (rising)
1 → Fall (falling)
1
0 → 0 to 20 mA
1 → 4 to 20 mA
2 → 0 to 10 V
0
0 to Max
(0.0% to Max)
1000
Min to 1000
(Min to 100%)
150
50 to 5000
(50 to 5000 ms)
www.gemu-group.com