GEM 533 eSyStep Operating Instructions Manual page 38

Motorized globe valve
Table of Contents

Advertisement

12 Specific data IO-Link (pin 6)
12.4.28 Stroke limiter
The upper and lower valve position of the control range can be set for the Stroke limiter parameter.
In-
Sub-
Off-
Access
dex
In-
set
Rights
dex
0xB6
1
R/W
2
R/W
Description of parameter values
Parameter
Max Pos
Min Pos to 1000
(Min Pos to 100.0%)
Min Pos
(0.0% to Max Pos)
12.4.29 Set value input
In-
Sub-
Off-
Access
dex
In-
set
Rights
dex
0xB8
1
R/W
2
R/W
3
R/W
4
R/W
5
R/W
Description of parameter values
Parameter
Set Value Direction
Set Value Type
I Min W
I Max W
(20.0 to 22.0 mA)
U Max W
(10.0 to 11.0 V)
GEMÜ 533
Positioner (Code S0)
Length
Parameter
16 bits
Max Pos
16 bits
Min Pos
Values
Set the stroke limiter of the control range in valve position OPEN.
0 to Max Pos
Set the stroke limiter of the control range in valve position CLOSED.
Length
Parameter
1 bit
Set Value Direction
2 bits
Set Value Type
8 bits
I Min W
8 bits
I Max W
8 bits
U Max W
Values
0
Specify direction of the set value input.
1
0 = Rise (rising)
1 = Fall (falling)
0
Determine signal input.
1
0 = 0 to 20 mA
2
1 = 4 to 20 mA
2 = 0 to 10 V
0 to 40
Determine minimum value of the current input. If the set value is not reached,
(0 to 4.0 mA)
the message "Set value too small" is issued.
200 to 220
Determine maximum value of the current input. If the set value is exceeded, the
message "Set value too high" is issued.
100 to 110
Determine maximum value of the voltage input. If the set value is exceeded, the
message "Set value too high" is issued.
Type
Default
uint:16
1000
uint:16
Description
Type
Default
uint:1
uint:2
uint:8
uint:8
uint:8
Description
38 / 52
Values
Min Pos to 1000
(Min Pos to 100.0%)
0
0 to Max Pos
(0.0% to Max Pos)
Values
0
0
1
1
0
1
2
35
0 to 40
(0 to 4.0 mA)
205
200 to 220
(20.0 to 22.0 mA)
103
100 to 110
(10.0 to 11.0 V)
www.gemu-group.com