12 Specific data IO-Link (pin 6)
12.4.32 Force settings
In-
Sub-
Off-
Access
dex
In-
set
Rights
dex
0xC0
1
R/W
2
R/W
Description of parameter values
Parameter
Force Valve
Force Init
Force settings
Actuator size
AS 0
GEMÜ 533
Positioner (Code S0)
Length
Parameter
10 bits
Force Valve
10 bits
Force Init
Values
0 to 1000
Set the force of the valve.
(0.0 to 100%)
0 to 1000
Set the force during initialization.
(0.0 to 100%)
Type
uint:16
uint:16
Description
Setting parameter
0 (0%)
500 (50%)
1000 (100%)
40 / 52
Default
Values
1000
0 to 1000
(0.0 to 100%)
550
0 to 1000
(0.0 to 100%)
Force in Newton
0
270
540
www.gemu-group.com