12.4.26 Open Close Tight
The sealing function can be set for the Open Close Tight parameter.
In-
Sub-
Off-
Access
dex
In-
set
Rights
dex
0xB2
1
R/W
2
R/W
Description of parameter values
Parameter
Open Tight
(80.0 to 100.0%)
Close Tight
12.4.27 Split range
The start and end of the set value range can be set for Split Range parameter.
In-
Sub-
Off-
Access
dex
In-
set
Rights
dex
0xB4
1
R/W
2
R/W
Description of parameter values
Parameter
Split Start
0 to Split End – 100
(0.0 to Split End –
Split End
Split Start + 100 to
(Split Start + 10.0%
www.gemu-group.com
Length
Parameter
16 bits
Open Tight
16 bits
Close Tight
Values
800 to 1000
Set the sealing function valve position OPEN.
0 to 200
Set the sealing function valve position CLOSED.
(0 to 20.0%)
Length
Parameter
16 bits
Split Start
16 bits
Split End
Values
Set the start of the set value range.
10.0%)
Set the end of the set value range.
1000
to 100.0%)
Type
Default
uint:16
uint:16
Description
Type
Default
uint: 16
uint: 16
1000
Description
37 / 52
12 Specific data IO-Link (pin 6)
Values
995
800 to 1000
(80.0 to 100%)
5
0 to 200
(0.0 to 20.0%)
Values
0
0 to Split End – 100
(0.0 to Split End – 10.0%)
Split Start + 100 to 1000
(Split Start + 10.0% to
100.0%)
Positioner (Code S0)
GEMÜ 533