Troubleshooting by Error Code
5.30 Discharge Pipe Temperature Abnormality
Applicable
All outdoor unit models
Models
F3
Error Code
Method of Error
Detect according to temperature detected with the discharge pipe or compressor body
Detection
thermistor.
Error Decision
When discharge pipe temperature becomes abnormally high (i.e., 135°C or more)
Conditions
When discharge pipe temperature sharply rises (remains at 120°C or more for a period of
Supposed
Abnormal discharge pipe temperature
Causes
Defective discharge pipe thermistor
Defective outdoor unit main PCB
Closed stop valve
206
consecutive 10 minutes)
SiME332106E
Part 6 Service Diagnosis