4.3.4. Mechanical

CAUTION
Do not over-tighten the pipe to piping boss.
CAUTION
Do not put excessive force on the inlet, outlet or drain connections of the valve.
PROHIBITION
Use of silicone or petroleum-based lubricants, oils or hydrocarbon-based lubricants, is
strictly prohibited with Foleo 5800 XTR as the valve 5800 is equipped with silicone o-rings
that are not compatible with silicone based lubricant.
MANDATORY
Use only P-80
damage the valve.
all plastic connections should be hand tightened. PTFE (plumber's tape) may be used on
connections that do not use an o-ring seal. Do not use pliers or pipe wrenches;
all plumbing must be completed according to local codes;
soldering near the drain line should be done before connecting the drain line to the valve.
Excessive heat will cause interior damage to the valve;
observe the drain line requirements:
maximum 1 m high at 2 bars inlet pressure. Add 50 cm for additional 1 bar at the softener's inlet;
do not use lead-based solder for sweat solder connections;
the valve is designed for minor plumbing misalignments. Do not support the weight of the
system on the valve fittings, plumbing, or the bypass;
it is not recommended to use sealants on the threads. Use PTFE (plumber's tape) on the threads
of the 25.4 mm (1") NPT elbow, the drain line connections, and other NPT/BSP threads.
4.4.

Integration constraints

Location of a water treatment system is important. The following conditions are required:
CAUTION
The surface for installation (platform or floor) must be solid, flat and level.
MANDATORY
Drain must be capable of handing a maximum backwash flow rate of 19 L/min.
locate the softener as close as possible from drain discharge point and within 12.2 m maximum
of drain discharge point, respecting minimum drain line diameter advises given at chapter 
4.5.7. Drain line connection, page 35;
room to access equipment for maintenance and adding salt in the brine tank;
constant electrical supply to operate the controller;
Ref. MKT-IM-038 / C - 15.11.2019
®