Installation
February 2020
Postrequisites
Continue with the grounding step.
3.7.2
Tank connection with flange
Prerequisites
Note
PTFE covered probes must be handled carefully to prevent damage to the coating.
Procedure
1. Place a suitable gasket on top of the tank flange.
2. Lower the transmitter and probe with flange into the tank.
50
Note
Gasket should not be used for PTFE covered probe with protective plate.
A. PTFE covered probe with protective plate
Reference Manual
00809-0100-4308
Rosemount 3308 Series