Emerson Rosemount 3308 Series Reference Manual page 225

Wireless guided wave radar
Table of Contents

Advertisement

Reference Manual
00809-0100-4308
Table E-3: Maintenance Alerts (M:)
Message
Low Signal Quality
Interface Measurement Lost
Capacity Denied
(1)
Location of the Alert in the HART command 48 Additional Status field.
Table E-4: Advisory Alerts (A:)
Message
Database Memory Warning
Non-Critical User Data Warning
Volume Range Warning
Verification Mode Active
Button Stuck
HiHi Level Alert
Hi Level Alert
Lo Level Alert
LoLo Level Alert
User Defined Alert
(1)
Location of the Alert in the HART command 48 Additional Status field.
Reference Manual
(continued)
(1)
Additional status
Byte 5::Bit 0
Byte 3::Bit 0
Byte 12::Bit 0
(1)
Additional status
Byte 0::Bit 2
Byte 2::Bit 1
Byte 4::Bit 7
Byte 4::Bit 4
Byte 1::Bit 5
Byte 5::Bit 4
Byte 5::Bit 5
Byte 5::Bit 6
Byte 5::Bit 7
Byte 5::Bit 3
Alert message mapping
Description
The Signal Quality is below the defined alert
limit.
No valid Interface reading. Reasons may be
multiple:
No valid surface echo peak in the
measuring range.
Incorrect transmitter configuration.
The device has failed to require all of the
necessary wireless bandwidth to broadcast at
the configured rate(s).
Description
The device has failed to write to the database
memory at some time in the past. Any data
written during this time may have been lost.
A user written parameter does not match
expected value.
The level measurement is outside the
configured volume range.
The device is in verification mode and is not
reporting actual information.
The button on the Electronics Board is
detected as stuck in the active position.
The level is above the defined limit.
The level is above the defined limit.
The level is below the defined limit.
The level is below the defined limit.
The variable has surpassed the user defined
limit.
February 2020
225

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 3308a