Emerson Rosemount 3308 Series Reference Manual page 213

Wireless guided wave radar
Table of Contents

Advertisement

Reference Manual
00809-0100-4308
Figure D-5: Probe Angle (α)
Remote housing
If the transmitter head is mounted apart from the probe, the length of cable between
probe and remote housing must be configured.
User defined probe settings
Parameters for user defined probe.
Note
These settings should only be modified for customized probes. The settings are typically
provided by factory.
Geometry
Calibration offset
Difference between surface distance measured by transmitter and the same distance
measured by, for example, hand-dipping with a measurement tape. A positive Calibration
Offset value will increase the presented level value.
It is recommended to run the Verify Level tool to match the product level reported by the
transmitter to a reference measurement.
Show level below probe end as zero
When this setting is selected and the product surface is at or below the probe end, the
level measurement output will be zero.
Note
Only applicable for negative probe end peak.
Reference Manual
Configuration parameters
February 2020
213

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 3308a

Table of Contents