Emerson Rosemount 3308 Series Reference Manual page 208

Wireless guided wave radar
Table of Contents

Advertisement

Configuration parameters
February 2020
Default update rate
This defines how often the broadcast message is sent to the gateway. Faster update rates
have an impact on the total communications traffic on the network, and power module
life.
Device display
Display mode
The display can be configured to different display modes: Disabled, On Demand, or
Periodic.
Table D-2: Display Modes
Option
Disabled
On Demand
Periodic
Related information
Diagnostic button screen sequence
Display variables
As default, the level variable will be displayed. If more than one variable is configured, the
display will toggle between the values of the chosen variables.
Units
The units for length, volume, and temperature are selectable. After appropriate units have
been selected, all configuration parameters and transmitter variables will be expressed in
these units.
Length unit
Used unit for Level and Interface Level values.
Volume unit
Used unit for Volume values.
Temperature unit
Used unit for Electronics Temperature value.
HART - Variable mapping
Primary variable
Primary dynamic variable in the HART protocol which will be assigned as a variable from
the device.
208
Description
The display is always turned off.
The display is by default turned off. Selected variable screens will only
appear in the end of the diagnostic button screen sequence.
The display shows selected variable screens in a periodic sequence. A new
screen will appear on each wireless update.
Reference Manual
00809-0100-4308
Rosemount 3308 Series