CTP Cabling Recommendations
22
Four-post rack—A freestanding open rack, either open or closed
The rack must have at least two mounting posts.
The distance between the mounting holes in the two posts must be 18.31 in. +/-.063
in., as specified in the EIA-310-D document.
An optional mounting kit is available for midchassis mounting. Contact your Juniper
Networks sales representative for more information.
CTP1000 Rack Requirements on page 21
CTP1000 Space Requirements on page 22
CTP1000 Rack Installation on page 22
If you use an enclosed rack for the device, ensure that there is a minimum of 3 in. of
clearance between the inner side wall and the system. This clearance space ensures
adequate air flow.
CTP1000 Mechanical Requirements on page 21
CTP1000 Rack Requirements on page 21
CTP1000 Rack Installation on page 22
To confirm proper equipment rack installation, verify the following:
Racks are installed and electrically grounded according to manufacturer instructions.
Equipment racks are anchored to the floor and, when possible, anchored to the ceiling
as well.
Equipment rack installations comply with applicable local, state, and national codes.
CTP1000 Mechanical Requirements on page 21
CTP1000 Rack Requirements on page 21
CTP1000 Space Requirements on page 22
We suggest that you comply with the following recommendations:
Ensure that cable distance and rate limits meet IEEE-recommended maximum speeds
and distances for signaling purposes. For information about attenuation and power
loss in optical fiber cables see: