M120 Router Power Requirements

88

Figure 25: M120 DC Power and Grounding Cable Lug

End vie w
0.28
diameter
0.55
each hole
0.08
0.25
0.625
If the 48 VDC facility is equipped with a circuit breaker rated at 60 A (-48 VDC), then the
grounding cable must be minimum 10 AWG, or as permitted by the local code. If the 48
VDC facility is equipped with a circuit breaker rated more than 60 A (-48 VDC) up to 100
A (-48 VDC), then the grounding cable must be minimum 8 AWG, or as permitted by the
local code.
NOTE:
Additional grounding is provided to an AC-powered router when you
plug its power supplies into grounded AC power receptacles.
M120 Router Chassis Description on page 7
Connecting the Grounding Cable to the M120 Router on page 151
Table 50 on page 88
lists the AC and DC power system electrical specifications.
Table 51 on page 89
lists the AC power supply electrical specifications.
lists the DC power supply electrical specifications.
requirements for various hardware components when the router is operating under typical
voltage conditions. For PIC power requirements, see the M120 Multiservice Edge Router
Interface Module Reference.

Table 50: Power System Electrical Specifications

Item
AC input voltage
AC input line frequency
AC system current rating
(per power supply)
2.25
Crimp area
0.37
All measurements in inches
Table 53 on page 89
Specification
Operating range: 100 to 240 VAC
47 to 63 Hz
28 A @ 100 VAC (15 A top inlet, 13 A bottom inlet)
14 A @ 240 VAC
10A WG conductor
Table 52 on page 89
lists the power