General Information; Airside Data; Electrical Data; Waterside Data - Trane PCC-1L-3210-4-7.5 Installation Instructions Manual

Low-temp air-handling unit
Table of Contents

Advertisement

General Information

Model Number . . . . . . . . . . . . . . . . . . . . . . . PCC-1L-3210-4-7.5
Ambient Operating Conditions . . . . . . . . . . . . -20°F to 100°F

Airside Data

Discharge Air Configuration . . . . . . . . . . . . . . . . . . . . Horizontal
Flex Duct Connection Qty & Size . . . .(1) 36 in. round
units
Nominal Air Flow (cfm) . . . . . . . . . . . . . . . . . . . . . . . . . 12,100
Discharge Static Pressure
@ Nominal Air Flow . . . . . . . . . . . . . . . . . . . . . . . . . . 1.5 in. ESP
Maximum Air Flow (cfm) . . . . . . . . . . . . . . . . . . . . . . . . . 24,500
Discharge Static Pressure
@ Maximum Air Flow . . . . . . . . . . . . . . . . . . . . . . . . . 0.5 in. ESP
1
For ambient conditions below 40°F, glycol is recommended.
2
With Long Throw Adapter
3
Actual airflow is dependent upon external static pressure requirement. Con-
tact Trane Rental Services for specific airflow and static pressure information.
Subject to change at any time without notice or liability.
Table 1.
Coil Capacity
Coil Type
Chilled Water
Selection based on 50% propylene glycol/water solution.
Selection is required for actual AHU performance.
Contact Trane Rental Services for specific selection
information.
Maximum waterside pressure is 150 psi (2.31' H
8
(4) 20 in. round (F1) units
Entering/Leaving
Water Flow
Water Temp (°F)
(gpm)
0/3.4
0/3.9
0/3.1
O = 1 psi)
2

Electrical Data

1
Supply Motor Size . . . . . . . . . . . . . . . . . . . . . . . . . . 7.5 hp/11 A
Heater Circuit . . . . . . . . . . . . . . . . . . . . . . . . . 37,730 W/47.35 A
Supply Motor Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . 1160 rpm
Fused Disconnect/Circuit Breaker . . . . . . . . . . . . . . . . . . . . . Yes
2
(F0)
Number of Electrical Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Voltage 460V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-phase
3
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Hz
Minimum Circuit Ampacity (MCA) . . . . . . . . . . . . . . . . . .. 61 A
Maximum Over current Protection (MOP) . . . . . . . .. . . . . 80 A
For additional electrical information contact Trane Rental
Services.

Waterside Data

Water Connection Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.5 in.
Water Connection Type . . . . . . . . . . . . . . . . . . . . . . . . . . Grooved
Drain Pipe Size . . . . . . . . . . . . . . . . . . . . . . . . . 2.0 in. (F0 Units)
Drain Pipe Connection Type . . . . . Female Pipe Thread (F0
Units) Garden Hose (F1 Units)
Water Damage!
Connecting all drains to a common line with only one
trap could result in condensate retention and possible
water damage to the air handler or adjoining space.
When more than one module has a drain pain, trap
each module individually.
Pressure Drop
(ft of H²O)
70
16.17
90
17.39
120
27.9
3/4 in. (F1 Units)
NOTICE
Entering/Leaving
Coil Capacity
Air Temp (°F)
(BTUH)
14/6.8
105,077
16/9.7
158,567
16/9.4
166,583
CHS-SVN011C-EN