Fan Section - Trane Climate Changer T Series Installation Operation & Maintenance

Table of Contents

Advertisement

Installation-Mechanical

Fan Section

Hazardous Voltage with Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor
start/run capacitors before servicing. Follow proper lockout/tagout procedures to
ensure the equipment cannot be inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane or others, refer to the
appropriate manufacturer's literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all capacitors have discharged.
Failure to disconnect power and discharge capacitors before servicing could result in
death or serious injury.
Note: For additional information regarding the safe discharge of capacitors, see
The fan section can be configured as draw-thru or blow-thru. Review the submittals and
unit tagging prior to assembly.
Figure 26. T-Series Isolator
Shipping
tie-down
bolt
40
WARNING
PROD-SVB06A-EN.
Adjusting
bolt
Jam nut
Adjusting
nut
Fan
base
The fan and motor assembly are internally isolated.
The fan and motor bases are bolted to a minimum of
four spring isolators. The isolators are secured to the
fan section support base. Shipping tie-down bolts are
bolted to the isolators between the fan base and the
isolator support frame (see
The shipping tie-downs secure the isolation base to
the support assembly to prevent any damage to the
fan section during shipment. The shipping spacers
must be removed prior to unit operation unless the
unit is to be externally isolated.
T-Series Climate Changer Air Handler IOM • CLCH-SVX06A-EN