Mains Connection; Reconnection Of Sectionalized Units; Wiring Requirements; Frequency Of Inspections - Trane CLCF Climate Changer Manual

Air handling units
Table of Contents

Advertisement

Factory engineered controls
Duct static pressure sensor
The duct static pressure sensor should be mounted in the supply ductwork, approximately two thirds of the distance
from the fan to the end of the longest run of ductwork. The sensor requires two pairs of screened cable to the control
panel.
One pair supplies power to the device and the other is the pressure signal from the device to the controller.
FWD
Power supply
Outside temperature sensor
Capacities
Cooling capacity on water (1)
The outside temperature sensor should be mounted on a Northfacing wall. It requires a single pair of screened wires.
Heating capacity on water (2)
The sensor can be factory mounted in the fresh air inlet. Other items are supplied loose on a project specific basis
Fan motor
and data sheets are available for these items.
Fan power input (3)
Current amps (3)
Start-up amps

Mains connection

Air flow
minimum
Mains connections are normally made through the bottom of the control panel. All the cables should be suitably
nominal
arranged so as not to put excessive strain on the terminals. They should be fitted with suitable glands to prevent
maximum
Main coil
water ingress.
Water entering/leaving connections

Reconnection of sectionalized units

Electric heater (accessory for blower only)
Electric power supply
If the unit is supplied in sections, the internal control wiring will have been disconnected in the factory between
Heating capacity
Hot water coil (accessory for blower only)
sections using break point connectors and the cables will be marked with identifiers. Site reconnection is to be done
Heating capacity (4)
by a contractor.
G2 filter (filter box accessory)
Quantity

Wiring requirements

Dimensions ( LxWxth)
G4 filter (filter box accessory)
Quantity
Running sensor wires in the same conduit or bundle with any AC power wires other than 24VAC may cause a
Dimensions ( LxWxth)
malfunction. With on site fitted items, the screened wire should be covered with insulation tape at the sensor
Condensate pump (accessory)
terminal box. Site mounted sensor cables should be Belden 8760 for 2 core devices and Belden 9402 for 4 core
Water flow - lift height
cables.
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Fire signal (option)
Sound pressure level (5)
Sound power level (5)
The AHU unit maybe interfaced to a fire alarm shut down by connecting a normally closed contact to the designated
Unit dimensions
terminals. If this is not required, the fire contacts are replaced by a link. Remote fireman's override switches can be
Width x Depth
connected to allow operation of the extract fan after a fire alarm has been actuated. Where a mixing box is fitted, the
Height
Shipped unit dimensions
exhaust air damper will be driven to the fully open position while the mixed air and fresh air dampers are driven
Width x Depth
closed.
Height
Override contacts can be connected to the designated terminals where this option has been ordered.
Weight
Colour
Filter section
Recommended fuse size
Unit alone (aM/gI)
Depending on the order, a common or an individual filter switch is provided to indicate when the filter section
Unit with electric heater (gI)
differential pressure is excessive. The filters may need to be changed.
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
Frost protection thermostat
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
In the event that the coil air on temperature drops below 5°C, a thermostat is provided to switch off the supply fan on
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
units with water coils. It is a hard-wired form of protection and can only be monitored by the controller. This prevents
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
hot water coils from freezing and would typically operate in cold weather if the hot water coil supply has failed.
Heat exchanger operating limits:
FWD:
Fan section
*water temperature: max 100° C
A pressure differential switch is provided across each fan to provide a proof of airflow indication. All fan / motor are
*absolute service pressure: min 1 bar/max 11 bars
belt and pulley driven.
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

Frequency of inspections

It is recommended to inspect all end devices supplied with the unit for correct operation and calibration on an annual
basis.

Recommended spare parts list

If required, a list of recommended components to be kept on site can be provided.
4
28
Technical Data
08
(V/Ph/Hz)
(kW)
5,2
(kW)
6,3
(type)
(kW)
0,23
(A)
1,1
(A)
3,2
(m
/h)
490
3
(m
/h)
820
3
(m
/h)
980
3
(type)
(Dia)
3/4"
(V/Ph/Hz)
230/1/50
(kW)
2/4
(kW)
6,3
2
(mm)
386x221x8
-
(mm)
-
(type)
(l/h - mm)
(dB(A))
36/40/43
(dB(A))
46/50/53
(mm)
890 x 600
(mm)
250
(mm)
933 x 644
(mm)
260
(kg)
32
(A)
8/16
(A)
16 (2kW),25 (4kW)
12
20
230/1/50
8,3
15
11,9
18,9
2 x direct drive centrifugal
0,46
0,65
2,2
3,1
5,5
9,3
980
1400
1650
2300
1970
2600
ISO R7 rotating female
3/4"
1 1/2"
230/1/50 or 400/3/50
400/3/50
8
10
12
17,4
2
2
486x271x8
586x321x8
2
2
486x264x48
586x314x48
Centrifugal
24 - 500
38/41/44
46/50/53
48/51/54
56/60/63
1090 x 710
1290 x 820
300
350
1133 x 754
1333 x 864
310
360
46
61
galvanised steel
8/16
8/16
40 (230V),3*16 (400V)
3*20
30
45
18,8
30,1
20,9
38,2
1,04
1,51
4,7
5,5
14,1
16,5
1800
2700
3000
4500
3600
5400
1 1/2"
1 1/2"
400/3/50
400/3/50
12
12
22,4
34,5
2
2
586*421*8
586*621*8
2
2
586*414*48
586*614*48
47/52/57
47/52/58
57/62/67
57/62/68
1290 x 970
1290 x 1090
450
650
1333 x 1008
1333*1133
460
660
76
118
8/25
8/25
3*25
3*25
UNT-PRC002-GB
AH-SVX03C-GB