(G) Control parameters
5.16.10
Regenerative brake selection and DC feeding
mode
• When performing frequent start and stop operation, usage rate of the regenerative brake can be increased by using
the brake resistor or the brake unit.
• It is possible to choose between the DC feeding mode 1, which will operate with DC power supply (terminals P and
N), and DC feeding mode 2, which will normally operate in AC power supply (terminals R, S, and T) and operate in
DC power supply (terminal P and N), such as batteries, at the time of power failure.
• While the power is supplied only to the control circuit, the reset operation when the power is supplied to the main
circuit can be selected.
Pr.
Name
30
Regenerative
E300
function selection
70
Special regenerative
G107
brake duty
599
X10 terminal input
T721
selection
The initial value or setting range for the standard model
The initial value or setting range for the separated converter type
Available only with the standard model
Details of the setting value
• FR-A860-01080 or lower
Regeneration unit
Provided brake resistor
,
Brake unit
Brake resistor other than the
provided brake resistor
For manufacturer's. Do not set.
• FR-A860-01440 or higher
Regeneration unit
Without regenerative function
For manufacturer's. Do not set.
• FR-A862-05450 or higher
Regeneration unit
Without regenerative function (FR-CC2)
For manufacturer's. Do not set.
For the FR-A860-00170 or lower.
For the FR-A860-00320 or higher.
For the FR-A860-00090 or lower.
While the power is supplied only to the control circuit with Pr.30 = "100 or higher", the inverter reset is not performed when the power is supplied to the
main circuit.
608
PARAMETERS
Initial
Setting range
value
0 to 2, 10, 11, 20,
21, 100 to 102,
110, 111, 120,
0
121
10
2, 10, 11, 102,
110, 111
0%
0 to 100%
0
0
1
1
Power supply
Pr.30
terminals of inverter
Setting
0 (initial
R, S, T
value), 100
P, N
10, 110
R, S, T/P, N
20, 120
R, S, T
1, 101
P, N
11, 111
R, S, T/P, N
21, 121
―
2, 102
Power supply
terminals of inverter
R, S, T
P, N
R, S, T/P, N
―
Pr.30 Setting
10 (initial value), 110
2, 11, 102, 111
Set the applied regeneration unit, the terminal used for power
supply, and whether to reset the inverter when the power is
supplied to the main circuit.
Set the %ED of the built-in brake transistor operation.
Normally open input
Normally closed input (NC contact input specification)
Pr.70
Setting
The regenerative brake duty will be as follows.
―
• FR-A860-00090 or lower: 2%
• Other than above: 0%
10%
―
6%
―
―
Pr.30 Setting
0 (initial value), 100
10, 110
―
20, 120
1, 2, 11, 21, 101, 102,
0% (initial value)
111, 121
Description
Remarks
Pr.70 Setting