Frequency Setting Voltage (Current) Bias And Gain - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

(T) Multi-Function Input Terminal Parameters
5.12.5
Frequency setting voltage (current) bias and
gain
The degree (incline) of the output frequency to the frequency setting signal (0 to 5 VDC, 0 to 10 V or 4 to 20 mA) is
selectable to a desired amount.
Use Pr.73 Analog input selection, Pr.267 Terminal 4 input selection, or the voltage/current input switch to switch
among input 0 to 5 VDC, 0 to 10 V, and 4 to 20 mA. (Refer to
Pr.
902
Terminal 2 frequency setting
T200
bias frequency
902
Terminal 2 frequency setting
T201
bias
125
903
Terminal 2 frequency setting
T022
T202
gain frequency
903
Terminal 2 frequency setting
T203
gain
904
Terminal 4 frequency setting
T400
bias frequency
904
Terminal 4 frequency setting
T401
bias
126
905
Terminal 4 frequency setting
T042
T402
gain frequency
905
Terminal 4 frequency setting
T403
gain
917
Terminal 1 bias frequency
T100
(speed)
917
Terminal 1 bias (speed)
T101
918
Terminal 1 gain frequency
T102
(speed)
918
Terminal 1 gain (speed)
T103
241
Analog input display unit
M043
switchover
402
PARAMETERS
Name
Initial value
0 Hz
0%
60 Hz
100%
0 Hz
20%
60 Hz
100%
0 Hz
0%
60 Hz
100%
0
page
393)
Setting
range
0 to 590 Hz
Set the terminal 2 input bias side frequency.
Set the converted % on the bias side voltage
0 to 300%
(current) of the terminal 2 input.
0 to 590 Hz
Set the terminal 2 input gain (maximum) frequency.
Set the converted % on the gain side voltage
0 to 300%
(current) of the terminal 2 input.
0 to 590 Hz
Set the terminal 4 input bias side frequency.
Set the converted % on the bias side current
0 to 300%
(voltage) of terminal 4 input.
0 to 590 Hz
Set the terminal 4 input gain (maximum) frequency.
Set the converted % on gain side current (voltage)
0 to 300%
of terminal 4 input.
Set the terminal 1 input bias side frequency
0 to 590 Hz
(speed). (speed limit)
Set the converted % on bias side voltage of
0 to 300%
terminal 1 input. (speed limit)
Set the terminal 1 input gain (maximum) frequency
0 to 590 Hz
(speed). (speed limit)
Set the converted % on the gain side voltage of
0 to 300%
terminal 1 input. (speed limit)
0
% display
1
V/mA display
Description
Select the unit for analog input
display