(D) Operation command and frequency command
5.9.2

Startup in Network operation mode at power-ON

When power is switched ON or when power comes back ON after an instantaneous power failure, the inverter can be
started up in the Network operation mode. After the inverter starts up in the Network operation mode, parameter writing
and operation can be commanded from programs.
Set this mode when performing communication operation using the RS-485 terminals or a communication option.
Pr.
Name
79
Operation mode selection
D000
340
Communication startup
D001
mode selection
Selecting the operation mode for power-ON (Pr.340)
• Depending on the Pr.79 and Pr.340 settings, the operation mode at power-ON (reset) changes as described below.
Pr.340
Pr.79
Operation mode at power-ON, at power res-
setting
setting
0 (initial
External operation mode
value)
1
PU operation mode
2
External operation mode
0
(initial
3, 4
External/PU combined operation mode
value)
6
External operation mode
X12 (MRS) signal ON External operation mode
7
X12 (MRS) signal OFF External operation mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
1, 2
3, 4
External/PU combined operation mode

6
NET operation mode
X12 (MRS) signal ON NET operation mode
7
X12 (MRS) signal OFF External operation mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
10, 12

3, 4
External/PU combined operation mode
6
NET operation mode
7
External operation mode

Use Pr.340="2 or 12" setting to perform communication with the RS-485 terminals.
Even if an instantaneous power failure occurs while Pr.57 Restart coasting time ≠ "9999" (with automatic restart after instantaneous power
failure), inverter continues operation at the condition before the instantaneous failure.

The operation mode cannot be directly changed between the PU operation mode and Network operation mode.

Switching between the PU and NET operation modes is available with the
Parameters referred to
???????
Pr.57 Restart coasting time
Pr.79 Operation mode selection
300
PARAMETERS
Initial
value
0
0
toration, or after a reset
page 515
page 291
Setting
range
Selects the operation mode.
0 to 4, 6, 7
(Refer to
page
291.)
0
Follows the Pr.79 setting.
The inverter starts up in the Network operation mode.
1, 2
If an instantaneous power failure occurs when "2" is set, the operating
status before the instantaneous power failure is maintained.
The inverter starts up in the Network operation mode. The operation
mode can be changed between the PU operation mode and Network
10, 12
operation mode from the operation panel.
If an instantaneous power failure occurs when "12" is set, running is
continued at the condition before the instantaneous power failure.
Switching among the External, PU, and NET operation
modes is enabled.
PU operation mode fixed
Switching between the External and NET operation modes
is enabled.
Switching to PU operation mode is disabled
Operation mode switching is disabled
Switching among the External, PU, and NET operation
mode is enabled while running.
Switching among the External, PU, and NET operation
modes is enabled.
External operation mode fixed. (Forcibly switched to
External operation mode.)
Same as Pr.340="0" setting
Switching between the PU and NET operation mode is
enabled

Same as Pr.340="0" setting
NET operation mode fixed
Same as Pr.340="0" setting
Switching between the PU and NET operation mode is
enabled while running.
Same as Pr.340="0" setting
key on the operation panel and the X65 signal.
Description
Operation mode switching


