(E) Environment setting parameters
5.7.2
Reset selection/disconnected PU detection/PU
stop selection
The reset input acceptance, disconnected PU (operation panel/parameter unit) connector detection function and PU
stop function (PU stop) can be selected.
Pr.
Name
Reset selection/
75
disconnected PU detection/
PU stop selection
E100
Reset selection
E101
Disconnected PU detection
E102
PU stop selection
E107
Reset limit
The parameters above will not return to their initial values even if parameter (all) clear is executed.

The setting range for the FR-A860-01080 or lower.

The setting range for the FR-A860-01440 or higher.
Pr.75
setting

0, 100
Reset command input always enabled.
Reset command input enabled only when the
1, 101
protective function activated.
Reset input enabled only when the start signal is
1000, 1100
OFF.
Reset input enabled only when the protective
1001, 1101
function is activated and the start signal is OFF.
2, 102
Reset command input always enabled.
Reset command input enabled only when the
3, 103
protective function activated.
Reset input enabled only when the start signal is
1002, 1102
OFF.
Reset input enabled only when the protective
1003, 1103
function is activated and the start signal is OFF.
244
PARAMETERS
Initial
value
14
0
0
1
0
Reset selection
Setting range
0 to 3, 14 to 17,
1000 to 1003,
1014 to 1017

For the initial setting, reset is always
0 to 3, 14 to 17,
enabled, without disconnected PU detection,
100 to 103, 114 to 117,
and with the PU stop function.
1000 to 1003,
1014 to 1017,
1100 to 1103,
1114 to 1117

0
Reset input is always enabled.
Reset input is enabled only when the
1
protective function is activated.
Reset input is enabled only when the start
2
signal is OFF.
Reset input is enabled when the protective
3
function is activated and the start signal is
OFF.
Operation continues even when the PU is
0
disconnected.
The inverter output is shut off when the PU is
1
disconnected.
Decelerates to a stop when the STOP key is
0
pressed in PU operation mode only.
Decelerates to a stop when the STOP key
1
for PU is pressed in any of the PU, external
and communication operation modes.
0
Reset limit disabled
1
Reset limit enabled

Disconnected PU
detection
Operation continues even when
PU is disconnected.
Inverter output shut off when PU
is disconnected.
Description
PU stop selection
The inverter decelerates to a
stop only when
is
pressed in the PU operation
mode.