Connection of stand-alone option units
2.10.2
Connection of the DC reactor
• When using the DC reactor, connect it across terminals P/+ and P1.
For the FR-A860-01080 or lower, the jumper connected across terminals P/+ and P1 must be removed. Otherwise, the
reactor will not be effective.
• Select a DC reactor according to the applied motor capacity. (Refer to
• For the FR-A860-01440 or higher, and when a 75 kW or higher motor is used, always connect a DC reactor.
• Select a DC reactor according to the following table.
Motor capacity (kW)
75
0.616
90
0.517
110
0.426
132
0.351
160
0.294
185
0.254
220
0.214
250
0.188
280
0.169
315
0.150
The power supply frequency of 60 Hz is assumed.
Class H or higher insulation is recommended.
Select a DC reactor for which its L value does not fall to 50% or below when the inverter overload current rating is 150% (ND rating).
NOTE
• The wiring distance must be within 5 m.
• As a reference, the cable gauge for the connection must be equal to or larger than that of the power supply cables (R/L1, S/
L2, T/L3) and the earthing (grounding) cable. (Refer to
66
INSTALLATION AND WIRING
Remove
the jumper
Reactor specifications
Reactor L value
(mH)
rated current (A)
124
149
182
219
265
307
365
414
464
522
P1
P/+
DC reactor
page
672.)
,
DC reactor
page
40.)