FR-A860-00090 or lower : -10°C to +40°C (non-freezing) (LD/ND/HD rating), -10°C to +30°C (non-freezing) (SLD rating)
Surrounding air
FR-A860-00170 to 01080 : -10°C to +40°C (non-freezing)
temperature
FR-A860-01440 or higher : -10°C to +50°C (non-freezing) (LD/ND rating), -10°C to +40°C (non-freezing) (SLD/HD rating)
Surrounding air humidity
95% RH or less (non-condensing)
Storage temperature
-20°C to +65°C

Atmosphere
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt, etc.)
Maximum 2500 m (For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500
Altitude/vibration
m increase in altitude.), 5.9 m/s

Available only when a vector control compatible option is mounted.

For PM sensorless vector control, refer to

In the initial setting for the FR-A860-00170 or higher, the starting torque is limited to 150% by the torque limit level.

Available only for the standard model.

This protective function is not available in the initial status.

Available only for the standard model.

Temperature applicable for a short time, e.g. in transit.
2

2.9 m/s
or less for the FR-A860-02890 or higher.
2
or less
at 10 to 55 Hz (directions of X, Y, Z axes)

page
684.
Common specifications
675