Installation of the inverter and enclosure design
2.3.5
Protruding the heat sink through a panel
When encasing the inverter of the FR-A860-02890 or higher to an enclosure, the heat generated in the enclosure can be
greatly reduced by protruding the heat sink of the inverter.
When installing the inverter in a compact enclosure, etc., this installation method is recommended.
Panel cutting
Cut the panel of the enclosure according to the inverter capacity.
FR-A860-02890
FR-A860-03360
200
30
INSTALLATION AND WIRING
6-M10 screw
484
200
Hole
(Unit: mm)
FR-A860-04420
662
300
Hole
6-M10 screw
300