Earth (Ground) Fault Detection At Start; Initiating A Protective Function - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.10.4

Earth (ground) fault detection at start

Select whether to enable/disable earth (ground) fault detection at start. When enabled, earth (ground) fault detection is
performed immediately after a start signal input to the inverter.
Pr.
Name
249
Earth (ground) fault
H101
detection at start
• If a ground fault is detected at start while Pr.249 = "1", the output-side earth (ground) fault overcurrent (E.GF) is displayed
and the outputs are shut off. (Refer to
• The Pr.249 setting is enabled during V/F control and Advanced magnetic flux vector control
• When the Pr.72 PWM frequency selection selection setting is high, enable the ground fault detection at start.
NOTE
• Because of the detection performed at start, the output is delayed by approximately 20 ms at every start.
• Use Pr.249 to enable/disable ground fault detection at operation start. Ground faults are detected always during operation
regardless of the Pr.249 setting.
5.10.5

Initiating a protective function

A fault (protective function) is initiated by setting the parameter.
This function can be used to check how the system operates at activation of a protective function.
Pr.
Name
997
Fault initiation
H103
• To initiate a fault (protective function), set the assigned number of the protective function you want to initiate in Pr.997.
• The value set in Pr.997 is not stored in EEPROM.
• When a protective function activates, the inverter trips, a fault is displayed, and a fault signal (ALM, ALM2) is output.
• The latest fault in the fault history is displayed while the fault initiation function is in operation. After a reset, the fault history
goes back to the previous status. (The protective function generated by the fault is not saved in the fault history.)
• Perform inverter reset to cancel the protective function.
• For the selectable parameter by Pr.997 and the corresponding protective functions, refer to
NOTE
• If a protective function is already operating, no fault can be activated by Pr.997.
• The retry function is disabled when a protective function has been initiated by the fault initiation function.
• If a fault occurs after a protective function has been activated, the protective function indication does not change. The fault is
not saved in the fault history either.
Initial value
Setting range
0
0
1
page
640)
Initial
Setting
value
range
The setting range is same with the one for fault data codes of
16 to 253
the inverter (which can be read through communication).
9999
Written data is not stored in EEPROM.
The read value is always "9999".
9999
With this setting, the protective function does not activate.
(H) Protective function parameter
V/F
V/F
V/F
Description
Without the earth (ground) fault detection at start
With the earth (ground) fault detection at start
Description
page
629.
PARAMETERS
Magnetic flux
Magnetic flux
Magnetic flux
5
GROUP
H
325