Appendix 2 International Standards - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Item
Plug-in option
Communication option
Installation size
Converter
DC reactor

For the FR-A860-00450 or lower, the height is increased because the wiring cover shape differs.
Installation precautions
• Removal procedure of the front cover is different. (Refer to
• Plug-in options of the FR-A700 series are not compatible.
• Operation panel (FR-DU07) cannot be used.
Wiring precautions
• The spring clamp type terminal block has changed to the screw type. Use of blade terminals is recommended.
Instructions for continuous use of the PU07 (parameter unit)
manufactured in September 2015 or earlier
• For the FR-A800 series, many functions (parameters) have been added. When setting these parameters, the parameter
names and setting ranges are not displayed.
• Only the parameter with the numbers up to "999" can be read and set. The parameters with the numbers after "999" cannot
be read or set.
• Many protective functions have been added for the FR-A800 series. These functions are available, but all faults are
displayed as "Fault". When the fault history is checked, "ERR" appears. Added faults will not appear on the parameter unit.
(However, MT1 to MT3 are displayed as MT.)
• Parameter copy/verification function are not available.
Copying parameter settings
• The FR-A700 series' parameter settings can be easily copied to the FR-A800 series by using the setup software (FR
Configurator2). Not supported by the setup software FR-SW3-SETUP or older.
NOTE
• For the installation size and the outline dimensions of the separated converter type, refer to the FR-A862 (Separated
Converter Type) Instruction Manual (Hardware).
Appendix 2
• For information on compliance with EU Directives or standards including UL or cUL standards, refer to both the Startup and
Hardware versions of the Instruction Manual.
FR-A760
Dedicated plug-in options (not interchangeable)
Connected to the connector 3
For standard models, installation size is compatible for all capacities. (Replacement between the same
capacities does not require new mounting holes.
For separated converter types, installation size is not compatible. (New mounting holes are required.)
Built-in for all capacities
The FR-A760-01040 or higher comes with a DC
reactor.
International standards
Connected to the connector 1
)

An optional converter unit (FR-CC2) is required for
separated converter types.
For the FR-A860-01440 or higher, and when a 75
kW or higher motor is used, select a DC reactor
suitable for the applicable motor capacity. (A DC
reactor is not included.)
Separated converter types (converter unit FR-CC2)
have a built-in DC reactor.
page
21.)
FR-A860
683
APPENDIX