Output Stop Function - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.16.8

Output stop function

The motor coasts to a stop (inverter output shutoff) when inverter output frequency falls to Pr. 522 setting or lower.
Pr.
Name
522
Output stop frequency
G105
• When both of the frequency setting signal and output frequency falls to the frequency set in Pr. 522 or lower, the inverter
stops the output and the motor coasts to a stop.
• At a stop condition, the motor starts running when the frequency setting signal exceeds Pr.522 + 2 Hz. The motor is
accelerated at the Pr.13 Starting frequency (0.01 Hz under PM sensorless vector control) at the start.
Example of when target frequency>Pr.522+2Hz, and start signal is ON/OFF
Target frequency
Pr.522+2Hz

The output frequency before the slip compensation is compared with the Pr.522 setting.
NOTE
• When the output stop function is valid (Pr.522  "9999"), the DC injunction brake (zero speed control, servo lock) becomes
invalid and the motor coasts to stop when the output frequency drops to the Pr.522 setting or lower.
Analog input command
Pr.522+2Hz
Pr.522
Output frequency
Pr.522+2Hz
Pr.522

At a stop condition, the motor is accelerated at the Pr.13 Starting frequency (0.01 Hz under PM sensorless vector control).

The output frequency to be compared with the Pr.522 setting is the output frequency before slip compensation (V/F control and Advanced
magnetic flux vector control), or the speed command value converted into the frequency (Real sensorless vector control, vector control, and PM
sensorless vector control).

Steepness of the slope depends on the acceleration/deceleration time settings such as Pr.7.
Initial
Setting
value
range
0 to 590 Hz
9999
9999
Output frequency
∗1
(fixed)
Pr.522
Pr.13
STF
RUN
Example of: target frequency = analog input command, start signal always ON
∗2
∗3
∗3
∗1
∗1
Pr.13
Inverter output
shutoff
STF
RUN
(G) Control parameters
Description
Set the frequency to start coasting to a stop (output shutoff).
No function
Inverter output shutoff
Inverter output
shutoff
Time
Time
Time
605
PARAMETERS
5
GROUP
G