5587001-YSG-A-520 | Start-Up & Operation Guide
LED Main Control Board Status Description
• PWR – LED is always ON (solid green) when
power is applied
• FLT – LED has a slow red flash when booting up
and fast red flashes when the unit is in FLT mode
• SA, MOD, EQ, FC – LEDs blink green when com-
municating
• LNK – LEDs blink green when ETH1/ETH2 are
connected to an Ethernet switch
• ACT – LEDs blink green when ETH1/ETH2 are
communicating

Setting Up Device Parameters

The local display or MAP gateway is used to configure
the communication parameters of the unit controller.
The key parameters are located in the Controller > Net-
work menu (see Figure 42 on page 96 and Table 28
on page 74).

Table 27: Cable Recommendations for BACnet MS/TP, Modbus, and N2

Bus and Cable Type
FC Bus: 22 AWG Stranded, 3-Wire
Twisted Shielded Cable
1
SA Bus (Terminal Block): 22 AWG
Stranded, 4-Wire, Two Twisted Pair
Shielded Cable
1
NOTE:
1. For best performance, it is strongly recommended to use a 3-wire, two twisted pair, 22 AWG stranded, shielded cable. A 22 gauge cable
offers the best performance for various baud rates, cable distances, and number of trunk devices primarily due to lower conductor-to-
conductor capacitance. Shielded cable offers better overall electrical noise immunity than non-shielded cable.

Table 28: BACnet IP Settings

IP address may change and may
DHCP
need to rediscover the router if the
Enabled
DHCP is enabled
The device ID is the instance number
for the BACnet device. This number
Device OID
must be unique across the building
networks for all device instances
Static IP
This IP address is used when DHCP
Address
enabled is false
Static IP
This IP mask is used when DHCP
Mask
enabled is false
Static IP
This IP router address is used when
Router
DHCP enabled is false
Address
Read-only status of the IP address
IP Address
in use
96
Non-Plenum Applications
Part Number
Anixter: CBL-22/3-FC-PVC
Belden
: B5501FE
®
Anixter: CBL-22/2P-SA-PVC
Belden: B5541FE
Description
Figure 42: Controller–Network Menu
When the unit is BACnet IP, attach a BACnet IP card
and configure the parameters shown in Table 28 on
page 96.
When the unit is BACnet MS/TP, remove the BACnet
IP communication card and configure FC bus comm
mode. Possible selections include: wired field bus,
wireless field bus, N2 field bus, and Modbus field bus
For BACnet MS/TP, configure the parameters shown in
Table 29 on page 97.
OD
0.138 inch
0.209 inch
User Action or Recommended Setting
BACnet IP – Dynamic
IP Address
TRUE
Set to the device OID
reserved for the unit
(not used)
(not used)
(not used)
Read-only status of the
Read-only status of the
IP address in-use
Plenum Applications
Part Number
Anixter: CBL-22/3-FC-PLN
Belden: B6501FE
Anixter: CBL-22/2P-SA-PLN
Belden: B6541FE
BACnet IP – Static IP
Default/Range
Address
FALSE
Set to the device OID
reserved for the unit
Set to the IP address
designated for the unit
255.255.255.255
Set to the IP mask for
the site
255.255.255.255
Set to the router IP
address for the site
255.255.255.255
IP address in-use
255.255.255.255
LD28040
OD
0.140 inch
0.206 inch
NA
0–4194302
0.0.0.0 to
0.0.0.0 to
0.0.0.0 to
0.0.0.0 to